GE Contactless Medium Read-Range Reader Model 260
15
Installation Notes (unless otherwise specified). 
All numbered items below are referenced on the appropriate wiring diagrams 
that follow.
1.
Fuse, power supply, door strike, protection device, and relay are provided by 
the installer.
2.
The 470 included 
Ω 
½-watt resistor, must be installed at the Micro/5 2RP 
terminal block. The Micro PX-2000/PXN-2000 and Micro/5 2RP and 8RP 
boards do not require this resistor.
3.
Shielded cable is recommended in electrically noisy environments.
4.
If using shielded cable: At the reader end: connect all shields together and 
insulate them. At the Micro end: connect the shield to the micro cabinet as 
indicated in the appropriate Micro Installation Manual.
5.
If using a local power supply, do not connect the power (8-30 VDC) line from 
the microcontroller to the reader. The ground line of the power supply must 
be connected to the micro (pin 2 on the reader connector). 
6.
7.
Blocking diodes may be 1N4148 or equivalent (installer supplied) and located 
in a secure area.
8.
Protection diodes may be 1N4002, 1N4003, or 1N4004 (installer supplied) for 
the door strike assembly.
9.
Install two 1k 
Ω 
¼-watt resistors (installer-supplied) at Door DI and Exit DI, 
as shown.
10. Connect a protection device across the door strike.
AC Door Strikes
: Connect an MOV (metal oxide varistor) across the door 
strike. (Included with Micro/5 2RP, 8RP, and PX(N)-2000).
DC Door Strikes
: Connect a diode across the door strike (cathode to positive 
side of door strike). (Included with Micro/5 2RP, 8RP, and PX(N)-2000).
11. Relay Coil Current Restriction (Micro/5 2RP with external relay).
The relay coil current must be limited to 40 mA to prevent damage to the 
board. Verify that the relay coil requires less than 40 mA.
12 VDC relay: coil resistance must be greater than 300 
Ω
.
The Micro/5 2RP with internal or AUX DO relay current through the relay 
contacts must be limited to less than 2 A to prevent damage to the 2RP. 
Current limiting may be achieved by using either a current-limiting power 
supply or by wiring in an external fuse.
12. Connect protection diode across relay coil. Connect a diode across the relay 
coil (cathode to positive side of relay coil).
General note
: Pair wires as shown in all wiring diagrams.