Lutron Electronics Co., Inc., 7200 Suter Road
Coopersburg, PA 18036-1299 U.S.A.
Test
Link
 B  Hold the indicated button on each transmitter 
for 6 seconds. The fixture will flash to show that 
wireless transmitters have been associated.  
To associate another transmitter, repeat steps 
4A and 4B.
 
A  Initiate association mode on the Project 37 Control Module by shining a green 
laser pointer at the laser detection hole on the sensor until the load attached to 
the Project 37 Control Module starts flashing every 2 seconds.
 
  Alternatively, press and hold the toggle button for 6 seconds on the Project 37 
Control Module to initiate association mode.
3
OR
Laser Detection (smallest)
Associate Wireless Transmitters to Project 37 Control Module
Before beginning this step, make sure that there are no other Project 37 Control 
Modules being set up in the building which are currently in this 
association mode.. It is possible that wireless transmitters from other systems can be incorrectly associated to this module.
  Green laser specifications: 
•  Wave output: constant
•  Wavelength: 532 nm
•  Output power: 5 mW maximum
Technical Assistance  |  1.800.523.9466  USA, Canada, and the Caribbean  |  +44.(0)20.7702.0657 Europe  |  +1.610.282.3800 Others  |  www.lutron.com     
041467 
Rev. A
07/2014
Part of the Energi TriPak
®
 Family
Project 37 
|
 Installation
+
For each fixture, ensure that you have:
One Project 37 Control Module
At least one Sensor or Pico
®
 Wireless Control
At least one 0 – 10 V Fluorescent Ballast or LED Driver
Required Components
Project 37 Occupancy/Vacancy and  
Daylight Sensor 
(1 maximum)
Pico
®
 Wireless 
Control
(10 maximum)
6 mA maximum for the control lines. Switches up to 1 A total. May be  
pre-installed in light fixture. 
Project 37 Control Module with 0 –10 V
Raise
Toggle
Lower
Load Status LED
Consult third-party 0 – 10 V fixtures installation guide for fixture-specific wiring. 
Start Here
+
Wireless Controls
On
All lights 100%
Favorite All lights 50%
Off
All lights off
Default Functionality
English
All Wireless  
Transmitters  
must be  
installed within  
30 ft (9 m) of the  
Project 37 Control Module.
Control: 0–10 V-  6 mA
Important Notes: Please read before installing.
For installation by a qualified electrician in accordance with all 
local and national electrical codes.
• Note: Use copper conductors only.
•  Check to see that the device type and rating is suitable for the 
application.
•  DO NOT install if product has any visible damage.
•  If moisture or condensation is evident, allow the product to dry 
completely before installation.
•  Operate between 0 °C and 40 °C, ambient.
•  0% to 90% humidity, non-condensing.
•  For indoor use only.
120 – 277  V~  50 / 60 Hz  1 A
FC-1 (Project 37 
Control Module)
UL 2043 Plenum Rated
12 V-  25 mA
FC-0  
(Project 37 Sensor)
Sensor
Pico
®
  
Wireless  
Control
Project 37 
Control 
Module
30 ft (9 m) max
40 ft (12 m)
30 ft (9 m)
Project 37  
Control Module
1
PIR Lens
Laser Detection
Daylight Lens
Note:  Project 37 Control Module can be used without a Sensor
Install control module directly to fixture or  
in junction box nearest the fixture. Install sensor 
in ceiling near fixture so as to optimize cover-
age in the desired area.
Radio Powr Savr
TM
 
Occupancy/Vacancy Sensor
(10 maximum)
Install Project 37 Control Module 
and Sensor
Suggested Installation Location: Close to the 
Fixture/Troffer.
 
  The Project 37 Control Module can be installed in a 
fixture/troffer, junction box or marshalling box using the 
conduit nut (provided) or with mounting screws (not 
provided). Please consult local and national electric 
codes for proper installation.
If installing unit inside a junction box, please see 
Application Note #423 at  
www.lutron.com/TechnicalDocumentLibrary/048423.pdf
 
B  Ideally mount the sensor to the ceiling tile close to the 
fixture using the wire form or using the command strips 
(included). The 2 communication wires from the sensor 
attaches to the control module poke in connectors. 
 
C  Once installed, energize the Project 37 Control Module.
Green/Yellow
Neutral
Switched 
Hot/Live
Violet
Gray
Fixture Earth
+
To additional 0 – 10 V fixtures
Hot (Black)
Neutral
+
NEU
HO
T
Class 2
MAINS
+
NEU
HOT
Class 
2
MAIN
S
Switched Hot (Red)
Hot (Black)
Neutral (White)
Neutral
Fixture/Troffer 
or Junction 
Box
1/2 in (21 mm) Knockout Opening
Conduit Nut
From back of sensor
Violet
Gray
Fixture Earth
Green/Yellow
WARNING! Shock Hazard. May result in serious injury or death.  
Turn off power at circuit breaker before installing the unit.
Spring arms
Note:  For solid ceilings or 
others where the wireform 
cannot be utilized, use the 
supplied Command strips 
to adhere sensor to desired 
location on ceiling or fixture.
Sensor Detection Range
2
Install the Sensor
The Project 37 sensor mounts to the ceiling surface with a supplied wireform clip. 
Two wires connect to the control module and can either be routed through a hole in 
the ceiling or across the ceiling surface. DO NOT install on ceilings higher than 12 ft 
(3.7 m). The sensor should be installed in a location where it has a good view of the 
space that it is meant to cover. 
15 ft 
(4.6 m)
9 ft 
(2.7 m)
3 ft 
(0.9 m)
0
3 ft 
(0.9 m)
9 ft 
(2.7 m)
15 ft 
(4.6 m)
400 ft
2
 (37 m
2
) maximum coverage 
area of one sensor when  mounted 
on an 9 ft (2.75 m) ceiling
Ceiling
Floor
9 ft  
(2.75 m)
15 ft 
(4.6 m)
9 ft 
(2.7 m)
3 ft 
(0.9 m)
0
3 ft 
(0.9 m)
9 ft 
(2.7 m)
15 ft 
(4.6 m)
15 ft 
(4.6 m)
9 ft 
(2.7 m)
3 ft 
(0.9 m)
0
3 ft 
(0.9 m)
9 ft 
(2.7 m)
15 ft 
(4.6 m)
 A
 
Slide closed end of wire form under 
the two retention arms on the back 
of the sensor
 B
 
While continuing to push against the 
retention arms, rock the other side of 
the wireform down against the sensor 
and slide them into place under the 
loop retention features
 C
 
Push wireform through tile and 
bend on the backside of the tile to 
complete the mounting.