Digital Security Controls Ltd. 143G4000 用户手册

下载
页码 22
3G4000 Wiring Diagrams
14
Figure 5 - Fire Alarm Control Unit and 3G Transmitter
 
 
 
 
 
 
 
 
 
 
 
         
  AUX Power 
(12V/700mA) 
RM1C ULC 
Relay 
Fire Alarm 
Control Unit 
TIP/RING 
Zone Input        
          
Outputs 
Fire
Trouble  
3G Wireless
Transmitter 
 
3G4000
T1/R1 
                
TIP/RING
Zone 
     
PGM2
Inputs        Output  
3G4000 cabinet 
3G (HSPA) or
2G (GPRS)
AC Input 
NOTES:
- Power for 3G4000 shall be provided from Fire 
Alarm Control Unit or separately Listed power supply 
rated for the application, 12V/700mA (Jumper JP3   
shall be set to on for Fire Monitoring). 
- All wiring connections must be run in a protective   
conduit. 
- For local supervision of the wireless transmitter connect 
PGM output from 3G4000 to one zone input on the 
Fire Alarm Control Unit. 
- Dry Contact Trouble output from ULC Listed Fire 
Alarm Control Unit must be connected to zone input 
on the 3G4000 for supervision of Tip/Ring connection. 
- Fire Alarms must be sent over both communication 
channels. Fire output from Fire Alarm Control Unit 
must be connected to the Input 1 on the 3G4000. 
- 24h Test Transmission must be enabled on the dialler 
and on the 3G4000. 
PSTN
Figure 6 - DSC Subscribers’ Unit Fire and 3G Transmitter Mounted in the Same Room
(
y
)
 
 
 
 
 
 
 
 
 
 
 
 
 
 
         
Fire Alarm 
Control Unit 
Outputs 
Fire
Supervisory 
Trouble 
DSC
Subscribers’ 
Unit Fire
Zone
Inputs
        TIP   
TIP            RING 
                 PGM1  
DSC Keypad 
LCD4501 
PK55XX
3G Wireless
Transmitter 
3G4000
T1/R1     
           TIP/RING 
Zone         
Input         PGM2 
AUX Power 
12V/700mA 
RM1C ULC 
Relay 
PC5003C
PC4050CR
cabinet
3G (HSPA)/2G (GPRS)   
PSTN
AC Input 
AC Input 
NOTES:
- Power for 3G4000 must be provided from Fire 
Alarm Control Unit or separately listed power 
supply rated for the application (12V/700mA)  
(Jumper JP3 shall be on for Fire Monitoring).
- All wiring connections must be run in a protective conduit.
- Phone Line Monitoring (TLM) must be enabled. 
- Connect PGM4 output from 3G4000 (Trouble 
Conditions) to a zone input on the Subscriber Unit 
for supervision of the GSM Transmitter. 
- 24hr Test Transmission over phone line (PSTN) and 
3G4000 must be enabled.  
- Fire Alarms must be sent over both communication
 channels.  
- On the Subscribers’ Unit, program PGM1 for 
PC1616/PC1832/PC1864 as System Event (Section 
[009] as type 10; Section [501] Fire Event option 2 
ON). An alternate option is to program PGM1 as Zone
Follower (Sec [009] = 29) and assign Fire Zone to PGM1
in Section [551].  Ensure Bit 3 is on in [501]. In this case,
a restored fire alarm condition does not require the DSC
control panel to be reset.
For PC4020 program PGM1 as type 49 Steady Fire ([00070049]). 
  
- Dry contact outputs from ULC Listed Fire Alarm 
Control Unit must be connected to zone inputs on 
the ULC Listed DSC Subscribers’ Unit Fire.
  
PC4020 
PC1864 
PC1832 
PC1616
RM1C ULC 
Relay 
3G4000 cabinet 
- Phone Line trouble is indicated by Yellow LED on 3G4000. 
- Refer to detailed diagrams in Figure 7.