ADCP-75-114 • Issue C • June 2001 
Page 8 
©
 2001, ADC Telecommunications, Inc. 
2.3 Mounting 
Procedure 
The
  RIU  may  be  either  rack-mounted  or  wall-mounted.  Of  the  procedures  that  follow,  use 
whichever
 procedure is appropriate for the installation.  
2.3.1 Rack-Mount 
Installation 
The
 RIU may be mounted in either a 19-inch or 23-inch EIA or WECO equipment rack. Both 
US
  standard  and  metric  machine  screws  are  included  for  rack  mounting  the  RIU.  When 
loading
  the RIU in a rack, make sure the mechanical loading of the rack is even to avoid a 
hazardous
  condition  such  as a severely unbalanced rack. The rack should safely support the 
combined
  weight  of  all  the  equipment  it  holds.  In  addition,  the  maximum  recommended 
ambient
 temperature for the RIU is 50º C (122º F). Allow sufficient air circulation or space 
between
 units when the RIU is installed in a multi-unit rack assembly because the operating 
ambient
 temperature of the rack environment might be greater than room ambient. 
 
  Warning:  Wet  conditions  increase  the  potential  for  receiving  an  electrical  shock  when 
installing
 or using electrically-powered equipment. To prevent electrical shock, never install 
or
 use electrical equipment in a wet location or during a lightning storm.  
Use
 the following procedure to install the RIU in the equipment rack: 
  1.  The RIU is shipped with the mounting brackets installed for 19-inch rack installations. If 
mounting
 the RIU in a 19-inch rack, proceed to step 4. If mounting the RIU in a 23-inch 
rack,
 proceed to step 2.  
  2.  Remove both mounting brackets from the RIU (requires TORX screwdriver with T20 bit). 
  3.  Reinstall both mounting brackets so the long side of the bracket is flush with the RIU 
front
  panel  as  shown  in  Figure  4.  Use  the  screws  removed  in  step  2  to  re-attach  the 
brackets
 to the RIU enclosure.  
16487-B
REMOVE AND REINSTALL MOUNTING
BRACKETS AS SHOWN FOR
 INSTALLATION IN 23-INCH RACKS
 
Figure 4. Installing the Mounting Brackets for 23-Inch Rack Installations