Controller Operation 
50 
AYC-F/G/M60 Series Installation and Programming Manual 
and if the door does not close prior to the end of this period, the 
controller activates the auxiliary relay. The auxiliary setting defines the 
door-ajar time. 
5.9.9.9
  Auxiliary Mode 8 
 
This mode controls the door indicator (right LED). 
The  right LED is not lit when: 
  A valid code is entered 
  While in Secure mode when waiting for Secondary code. 
Auxiliary input function: Green LED control 
Auxiliary output activated by: Valid user code, Auxiliary code 
For example, in Auxiliary Mode 8, the controller can function as a 
2-door controller and also provide LED indicator functionality control. 
The auxiliary relay is connected to the lock on the second door. The 
auxiliary setting defines the Door Open time for the second door. The 
auxiliary input is used to control the door indicator (right LED). If the 
auxiliary input is open, the right LED flashes green; if the auxiliary 
input is closed, the right LED flashes red. 
5.9.9.10
  Auxiliary Mode 9 
 
This mode controls the door indicator (right LED). 
The  right LED is not lit when: 
  A valid code is entered 
  While in Secure mode when waiting for Secondary code. 
Auxiliary input function: Red LED control 
Auxiliary output activated by: Valid user code, Auxiliary code 
For example, in Auxiliary Mode 9, the controller can function as a 
2-door controller and also provide LED indicator functionality control. 
The auxiliary relay is connected to the lock on the second door. The 
auxiliary setting defines the Door Open time for the second door. The 
auxiliary input is used to control the door indicator (right LED). If the 
auxiliary input is open, the right LED flashes red; if the auxiliary input 
is closed the right LED flashes green.