Honeywell International Inc. WFSRM 用户手册

下载
页码 68
SWIFT™ Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000NF-E:C  5/8/2015
61
LED Indicators
LED Pattern
Condition
Action Required
Bootloader 
normal
Slot request 
rejected
Mesh forming
Sustained tamper
Bootloader 
firmware update
Profile received
Battery check: all 
batteries are fresh
Profile removed
Device is ready to update.
Device is not permitted 
into the mesh.
Device is part of the mesh 
and looking for devices that 
are not in the mesh.
New application code is 
being downloaded.
Device is now profile 
assigned.
Maximum life of installed 
batteries remaining in 
device
Device has returned to the 
factory default mode.
Legend
Number of blinks
LED color
Interval between blink patterns
Duration of LED state
Indicates value is approximate
Two blinks in this pattern
First blink is green. Second is yellow
7 seconds between blink patterns
Will transition to next state after 
approximately 20 minutes
Example:
All units are in seconds. Minute is indicated by “M”.
Confirm device count and 
software version.
Device is tampered.
Solid
Solid
Distributor mode
Device is distributing its 
profile to other devices 
which requested a profile.
le
dd
ev
1
.wmf
8
7
20
M
15
5
1
10
2.5
0.5
Ensure detector is seated in the 
base and the module has the 
faceplate on.
14
7
3
M
Rescue mode
Device is functioning as 
normal and searching for 
lost devices.
Normal mode or 
tested walk test
Device is distributing as 
normal or it has been 
tested in a walk test.
7
20
M
Device LED Patterns
Use SWIFT Tools to initiate 
download.
Self test fail
Low battery cut-off
Device has failed internal 
self diagnostics.
Device is functioning.
Replace batteries.
Restart the device. If problem 
persists, contact technical support.
1
Solid