Toshiba IPE002Z 用户手册

下载
页码 89
 
E6581741 
- 10 - 
EtherNet/IP parameters 
Title 
Communi
cation No. 
Function Description 
Factory 
setting
c536 
C536 EtherNet 
Error 
Monitor of the EtherNet error. 
0: No error/clear error 
1: Modbus TCP IO Scanning timeout 
2: Network overload 
3: Loss of Ethernet carrier 
c554 
C554 
Web service (*3) 
Enables web server. 
0: Disable 
1: Enable 
c555 
C555 Drive 
Status 
Monitor the inverter status. 
3: Gate Block 
4: Run 
23: Fault 
 
Modbus TCP parameters 
Title 
Communi
cation No. 
Function Description 
Factory 
setting
c600- 
c603 
C600- 
C603 
IP Master (*3) 
The IP address for PLC(Master) of the Modbus TCP. 
0.0.0.0
c604 
C604 
IO Scan active (*3) 
Enables IO Scan function. 
0: Non-active 
1: Active 
(*3): This parameter is effective by reset. Please reset (power supply reset or f899=1) after changing a set point. 
 
 
  Warning
 
 
 
Mandatory 
action 
 
Set up “Communication error trip function (c100 to c103 and c523)” to stop the 
inverter when EtherNet/IP™ - Modbus® TCP communication is deactivated. 
 
When the parameters are changed, please reset 
(power supply reset or f899=1)
 the 
inverter for the changes to take effect.