Toshiba IPE002Z 用户手册

下载
页码 89
 
E6581741 
- 14 - 
3.2.4. Command
 data (c001-c006), Monitor data (c021-c026)
 
The outline is indicated about the setting item of parameter c001 – c006 and 
c021
 – c026 in Instance 102/152 and 105/155 of use. Please refer to a 
communication functional description for details. 
 
3.2.4.1. How to use Instance 102/152 and 105/155 
Instance 102/152 and 105/155 choose a command or the monitor of the driving state by a menu of c001 
- c006 and c021 - c026 and can perform the communication that is cyclic of EtherNet/IP™ and 
Modbus
®
 TCP (ID = 255). 
 
Example 1: Command transmitting by output Instance 102 
If the command value “c400” set to parameter fa06, Choose parameter fa06 (a communication 
option command) for command data (c001=1 (fa06)). 
 
For example, please set C400 in FA06 when you want to send the command from an EtherNet/IP™ 
option and the availability of the frequency order and a driving order. (Please refer to ” 3.2.4.2”) 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Example 2: State monitoring by the input instance 152. 
When you want to monitor the output current, set “3 (fd03)” to parameter c021. 
The value of the parameter 
fd03
 
specified as 0 and 1 byte of the input instance 152 with the parameter 
c021
 is inputted. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
VF-MB1/S15 
IPE002Z 
"0xC400" is set to parameter fa06 
Byte Value 
0 00 
1 C4 
2 ... 
3 ... 
... ... 
EtherNet/IP Master 
Parameter Value 
c001 
1 (fa06) 
c002 
... 
c003 
... 
... ... 
Output Instance 102 
Parameter Value 
c021 
3 (fd03) 
c022 
... 
c023 
... 
... ... 
The value of a parameter fd03 (0x1234)   
is outputted. 
Byte Value 
0 34 
1 12 
2 ... 
3 ... 
... ... 
Input Instance 152 
VF-MB1/S15 
IPE002Z 
EtherNet/IP Master