Toshiba IPE002Z 用户手册

下载
页码 89
 
E6581741 
- 66 - 
8.5.  "06 (0x06) Write Single Register" function 
This Modbus request is used to write a given value (Present Data) to the address 
supplied (Register Address). 
 
Request format: 
Byte Meaning 
Function Code = 06h 
Register Address Hi 
Register Address Lo 
Preset Data Hi 
Preset Data Lo 
 
Response format: 
Byte Meaning 
Function Code = 06h 
Register Address Hi 
Register Address Lo 
Preset Data Hi 
Preset Data Lo 
 
Exception response format: 
Byte Meaning 
Function Code = 86h 
Exception Code =   
01 (Illegal Function) 
02 (Illegal Data Address) 
03 (Illegal Data Value) 
04 (Slave Device Failure) 
 
 
 
Notes
 
 As for the EEPROM parameter, first the data is written to RAM, after that the data is written to 
EEPROM. Some EEPROM parameters cannot be changed during the inverter is running. 
When write to EEPROM parameter that will change inverter status from stop to run, the inverter must 
be in the state that it cannot run. 
For example: To write to EEPROM, the inverter must open ST-CC. (display shows "OFF") 
If not, the data is only written to RAM. 
 The Life of EEPROM is approximately 100,000 times. Avoid writing a command more than 100,000 
times to the same parameter of the Inverter.   
 Please access only parameters in document.