E6581741 
- 68 - 
8.7.  "23 (0x17) Read/Write Multiple Registers" function 
The "Read/Write Multiple Registers" service is reserved for setting up the IO Scanning 
service (see "IO Scanning" section) 
 
Request format: 
Byte Meaning 
Function Code = 17h 
Starting Address Hi 
Starting Address Lo 
No. of Registers Hi (0) 
No. of Registers Lo (1 - 100) 
Byte Count (B = 2 × No. of Registers) 
First Register Data (Hi) 
First Register Data (Lo) 
・・・
 
・・・・・・・・・・・・・・・・
 
B+4 
Last Register Data (Hi) 
B+5 
Last Register Data (Lo) 
 
 
Response format: 
Byte Meaning 
Function Code = 17h 
Starting Address Hi 
Starting Address Lo 
No. of Registers Hi (0) 
No. of Registers Lo (1 - 100) 
 
 
Exception response format: 
Byte Meaning 
Function Code = 97h 
Exception Code =   
01 (Illegal Function) 
02 (Illegal Data Address) 
03 (Illegal Data Value) 
04 (Slave Device Failure)
 
 
 
Notes
 
 As for the EEPROM parameter, first the data is written to RAM, after that the data is written to 
EEPROM. Some EEPROM parameters cannot be changed during the inverter is running. 
When write to EEPROM parameter that will change inverter status from stop to run, the inverter must 
be in the state that it cannot run. 
For example: To write to EEPROM, the inverter must open ST-CC. (display shows "OFF") 
If not, the data is only written to RAM. 
 The Life of EEPROM is approximately 100,000 times. Avoid writing a command more than 100,000 
times to the same parameter of the Inverter.   
 Please access only parameters in document.