13.1.6  Low pressure Prevention control (Gas Leakage Detection) 
1. When the conditions listed in the table occur, the compressor stops and restarts after three minutes. 
2.  If this continuously occurs for twice within 20 minutes, all indoor and outdoor relays will be cut off. 
3. This control is not applicable for deice operation. 
Comp Frequency 
45 Hz or above 
64 Hz or above 
58 Hz or above 
73 Hz or above 
Total Outdoor Current 
1b
İ1˘3 1bİ1˘1.6 1bİ1˘1.3 1bİ1˘1.6
Indoor Piping Temp 
20
ć or above 
25 
ć or less 
20 
ć or above 
25 
ć or less 
Operation Mode 
Cool/Dry 
Heat 
Cool/Dry 
Heat 
Model RE9JKX 
RE12JKX 
13.1.7  Low Operation Frequency Protection Control 
If all following conditions exists, the compressor will run with the frequency of 40 Hz (RE9JKX, RE12JKX) or 30Hz 
(RE15JKX) 
Models RE9JKX, 
RE12JKX 
RE15JKX 
Intake Air Temp. 
ı30 ć or ˘15 ć
------------------- 
ı30 ć or ˘14 ć
ı28 ć or ˘14 ć
Outdoor Temp. 
ı38 ć or ˘16 ć
ı24 ć or ˘4 ć
ı38 ć or ˘13 ć
ı24 ć or ˘4 ć
Indoor Piping Temp. 
˘30 ć
ı0 ć
˘30 ć
ı0 ć
Operation Mode 
Cool / Dry 
Heat 
Cool/ Dry 
Heat 
13.1.8  Compressor Tank Temperature Rise Protection Control 
a. Control start conditions 
• For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A. 
• During Cooling and Soft Dry operations: 
Indoor suction temperature - indoor piping temperature is below 4
к.
Indoor temperature and outdoor temperature is 30±5
к.
Remote Control setting 16
к and Hi Fan Speed. 
• During Heating operations: 
Indoor piping temperature - indoor suction is under 5
к.
Indoor temperature and outdoor temperature is 20 ± 2
к.
Remote control setting 30
к and Hi Fan Speed. 
b. Control contents 
• Compressor stops (and restart after 3 minutes) 
• If the conditions above happen 2 times within 20 minutes, the unit will: 
- Stop operation 
- Timer LED blinks and “F91” indicated 
13.2  Protection Control For Cooling and Soft Dry Operation 
13.2.1  Outdoor Air Temperature Control 
• The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the 
diagram below. 
• This control will begin 1 minute after the compressor starts. 
• Compressor frequency will adjust base on outdoor air temperature. 
                      RE9JKX, RE12JKX                                                                          RE15JKX 
Outdoor air temp.(
к.)
38
25
18
11
free
Free
38
26
16
37
22
15
8
Outdoor air temp.(
к.)
38
25
18
11
free
16
26
37
47
37
22
15
8