Panasonic CU-RE9JKX 用户手册

下载
页码 51
38
13.2.2  Freeze Prevention Control 
1 .Frequency of the compressor 
For prevention of freezing of the indoor evaporator, the frequency of the    compressor will be changed according 
to the indoor piping temperature. 
2 .Indoor Fan Control 
Indoor fan speed changes according to the indoor piping temperature. 
13.2.3  Dew Prevention Control 
• To prevent dew formation at indoor unit discharge area. 
• This control starts if all conditions continue for 20 minutes: 
- Operated with Cooling or Soft Dry Mode. 
- Indoor intake temperature is between 25
к and 29к.
- Outdoor air temperature is less than 30
к.
• This control stopped then receive air swing change signal from Remote Control. 
13.2.4  Overload Protection for Cooling Operation 
The frequency for the compressor will change according to the outdoor piping temperature. 
13.3  Indoor Piping Air Temperature Control (Heating) 
13.3.1  Indoor Fan Control 
1. Indoor fan is controlled by the indoor piping temperature. 
ϥ  Manual Fan Speed 
Piping Temperature(
к)
K0 K1 K2 K3 K4 K5 K6
K7 K8 K9 K10
K11
16 19 24 32 32 36 36 39 54 54 57  60 
63
к
.
Outdoor pipe Temp.
61
к
60
к
56
к
RE9JKX, RE12JKX 
RE15JKX
58
к
9
к.
8
к.
6
к.
0
к.
Max.:40 Hz   Min.: 30Hz