14. Troubleshooting 
Guide 
14.1  Refrigeration cycle system 
In order to diagnose malfunctions, make sure that there are no 
electrical problems before inspecting the refrigeration cycle. Such 
problems include insufficient insulation, problem with the power 
source, malfunction of a compressor and a fan. The normal outlet 
air temperature and pressure of the refrigeration cycle depends on 
various conditions, the standard values for them are shown in the 
table on the right. 
14.1.1
Normal Pressure and Outlet Air Temperature (Standard)
Gas Pressure 
Mpa
(kg/cm
2
G)
Outlet air 
Temperature 
(°C)
Cooling Mode 0.9~1.2 ( 9~12) 
12~16 
Heating Mode 2.3 ~2.9 (23~29) 
36~45 
Condition:  Indoor fan speed = High 
Outdoor temperature = 35°C at cooling mode   and 7°C at 
heating mode. 
Compressor operates at rated frequency 
Different in the intake 
and outlet 
air temperatures 
Normal 
Value of electric current 
during operation 
Dusty condenser 
preventing heat radiation
Excessive amount 
of refrigerant 
x
Measuring the air 
temperature different
x
Measuring electric 
current during operation
x
Measuring gas side 
pressure
More than 8
̓C
(15 minutes after an operation 
is started) at cooling mode. 
Above 14
̓C (15 minutes after 
an operation is started.) at 
heating mode 
Less than 8
̓C at the cooling mode 
Less than 14
̓C at the heating mode 
Higher than specified
Lower than 
specified
Gas side 
pressure 
Inefficient compressor
Insufficient refrigerant
Clogged strainer or 
capillary cube 
Cooling 
Mode
High
Low
Low
Inefficient compressor
Insufficient refrigerant
Clogged strainer or 
capillary cube 
Heating 
Mode
Low
Low
Low