CH 5/ Start Menu
Selecting 
current probe 
(continued)
Other relevant 
information on 
current probes 
Refer to Chapter 2 Voltage Measurement Cable and Current Probe Connections for 
illustrations of typical current probes and for guidelines on how to connect current 
probes.
Refer to Appendix A for descriptions and part numbers of probes and adapter cables.
Refer to Appendix B for Dranetz-BMI current probes technical specifications.
Action...
Result...
STEP 2: (continued)
• Press OK to accept probe 
selection and monitor current.
• Press Cancel to retain previous 
probe settings and return to 
previous screen.
STEP 3: You need to set the CT 
scale factor when using a current 
probe that is not on the list. 
Pressing Scale will show the 
numeric window to enter the CT 
scale factor on the current probe. 
Use the keypad to set the CT scale 
factor. See sample scale factor 
calculation on page 5-10.
• Press OK to accept the CT 
scale factor value. The screen 
shown in Step 2 will be 
displayed.
• Press 
...
 
....
 if you want to clear 
and retype numeric values.
• Press x1000 to multiply the 
value by 1000.
• Press Cancel to discard 
changes and return to the 
previous screen (screen shown 
on Step 2).