Novatek THREE-PHASE POWER LIMITER OM-310 OM-310 数据表

产品代码
OM-310
下载
页码 28
- 5 - 
NOVATEK-ELECTRO
                                                                                                                                                       
ОМ-310
 
 
- PC, connected to one of OM-310 interfaces (MODBUS, RS-232). 
 
Table 1.4 - Measured and Displayed Parameters 
 
Measurement functions 
Range 
Accuracy 
Mnemonics 
Address  Measurement 
units used at 
data transfer 
Currents 
 
 
 
 
1/10 of an 
ampere* 
Phase currents RMS values, A 
0,5-999  
2% 


100,101, 
102 
Zero sequence current RMS value, A 
0,3-9,9  
2% 

103 
Each phase average current value at 
time specified in tSi parameter 
 
 

 
104,105, 
106 
Мах  each phase average current  value 
obtained (was obtained) since last power 
on. 
All average values can be reset with 
RES/MEM/SEL  button at time of max 
average current value output for any 
phase  (real-time average current value 
for corresponding phase is assigned). 
<3 I
tt
 
> 3 I
tt
 
2% 
10% 


 
107,108, 
109 
Negative sequence  current (current im-
balance), A. 
0,2-200 
5% 

110 
Voltages 
 
 
 
 
Volts 
Phase voltages RMS values (defined by 
connecting zero wire to OM-310), V 
100-300 
3 V 



111,112 
113 
Power voltage RMS values, V 
100-450 
В 



114,115 
116 
Positive-sequence voltage, V 
100-300 
3 B 

117 
Negative-sequence voltage, V 
3 -300 
3 B 

118 
Zero-sequence voltage (vector sum of 
three phase voltages,  divided by three),  
(measurement is possible only when ze-
ro wire is connected to OM-310),V 
3-100 
3 B 

119 
Wattages and Cosines 
 
 
 
 
 
Gross power, KVA** 
0-5000 
5% 

120, 121 
W * 10 
Active power, KW** 
0-5000 
5% 

122, 123 
Wattles power, KVAr** 
0-5000 
5% 

124, 125 
Phase A active power, KW** 
0-5000 
5% 

126, 127 
Phase B active power, KW** 
0-5000 
5% 

128, 129 
Phase C active power, KW** 
0-5000 
5% 

130, 131 
Phase 
А voltage/current angle cosine     
 
0,00-1,00 
5% 

132 
Cosine value 
*1000 
Phase B voltage/current angle cosine     
 
0,00-1,00 
5% 

133 
Phase C voltage/current angle cosine    
 
0,00-1,00 
5% 

134 
Time before load disconnect tripping when 
the load wattage is exceeded, sec **** 
0-600 
1s 

135 
seconds 
 
 Time before AR delay termination, sec***  0-900 
1s 

136 
Wait time after de-energizing in case of 
over wattage (indicates wait time before 
permit of system restart ), min **** 
0-30 
1s 

137 
Mains frequency, Hz 
45-65 
1% 

138 
1/10 Hz