ОМ-310
                                                                                                                                                       
NOVATEK-ELECTRO
 
Note. When working with external transformers of rated current over 100A, the currents (measured and cal-
culated), except for the zero sequence current (ground fault) are transferred via RS-232/RS485 in amperes. 
** Note. If power consumed by the load is over 999 kW (kVA, kVAr), then MW (MVA, MVAr) is displayed on 
screen with a “
п” – shaped point in the middle position. For instance, if the display shows 3п4”, it means  3.4 
MW (MVA, MVAr).  
*** Note. If automatic reset is forbidden, "not" message is displayed. 
**** Note. If the time is not defined, "---" is displayed on screen.  
1.2.3 Programmable parameters and their variability ranges are shown below in table 1.5. 
 
Table 1.5 - Programmable parameters  
                                                                                                                                         
Settings and read-off 
parameters  
Code pa-
rameters 
Minimum 
values 
Max. 
values 
Default 
setting 
Operation 
Address 
Transformers 
 
 
CT in use 

0-intergrated CT are in use 
1-external CTs are in use 
150 
CT rated current, A 

20 
800 
100 
For an external CT 
151 
CT rated current, A 

700 
10 
Used for calsculating the current and 
the time of overcurrent protection  
152 
Power Control 
 
 
Rated
 
power
 
of load, kW 

450 
 
153 
Power limiter tripping 
thresholds calculation 
parameter  

0 – threshold calculation for each 
phase (power handling capability for 
each phase equals Pnn/3) 
1 – threshold calculation for each 
phase +20% (total power for al pha-
ses equals Pnn, but not more than 
Pnn*1,2/3 for each phase) 
2 – aggregate threshold calculation 
(total power for all phases equals Pnn) 
154 
Main threshold, % 

50 
150 
110 
 
155 
Additional threshold*, % 

30 
100 
90 
 
156 
Time before load relay 
de-energizing, sec 
(main threshold) 

300 
60 
Time before load disconnect tripping 
when the load wattage main threshold 
is exceeded  
157 
Time while load relay is 
open, min 
(main threshold) 

60 
Time during which load relay is open 
after tripping when the load wattage 
main threshold is exceeded  
158 
Time before characteriz-
ing relay de-energizing*, 
sec 
(additional threshold) 

300 
10 
Time after which the characterizing re-
lay will open after tripping when the 
load wattage main threshold is ex-
ceeded  
159 
Time while the charac-
terizing relay is open, 
min (additional thre-
shold)  

60 
Time during which the characterizing 
relay is open after tripping which take 
place when the load wattage main 
threshold is exceeded  
160 
Additional threshold of 
the characterizing relay 
closure, % 

100 
30 
Threshold for the characterizing relay 
closure after overload triggered 
opening  
161 
Characterizing relay 
operation mode 

0 - the relay is used as an alarm relay 
1- the relay is used as a time relay 
(closes after time specified in 
 pa-
rameter after load relay closure ) 
2-the relay is used for connecting addi-
tional load 
3- the relay will close when load wat-
tless power threshold 
 is exceeded 
4- relay will be switched on after ex-
ceeding of main tripping 
162 
Characterizing relay 
activation mode when 
 

0 – relay will close after expiration of 
time 
 
1 – relay will close after reduction of 
consumed wattage  to level 
 
163