Here are described the basic operating procedures (In case of KT4).
Operating Procedure
Step 1 - Initialization
Step 1 - Initialization
In auxiliary function setup mode 2,
select entry type, alarm behavior,
control behavior, etc.
select entry type, alarm behavior,
control behavior, etc.
Step 2 - Calibration
In ancillary setup mode, set the PID
and alarm values.
and alarm values.
Step 3 - Lock Setup
In auxiliary function setup mode 1, set
the setting lock, SV max, and SV min.
(If Step 3 is not necessary, proceed to
Step 4.)
the setting lock, SV max, and SV min.
(If Step 3 is not necessary, proceed to
Step 4.)
Step 4 - Operation Setup
In main setup mode, set the SV (target
value).
value).
Sample configuration:
Input sensor:
K thermocouple (–200 to 1,370
°
C)
Control method:
PID
Alarm behavior:
Max alarm (deviation setting)
Control behavior: Inverse (heat)
A1 setting:
A1 setting:
50
°
C
122
°
F
SV (target value): 150
°
C
302
°
F
AT setting:
Run AT
To set up the system as shown above:
1) In Step 1 - Initialization, set the necessary values in auxiliary function
setup mode 2.
2) In Step 2 - Calibration, set the necessary values in ancillary setup mode.
3) In Step 4 - Operation Setup, set the SV (target) value in main setup
mode, and begin control.
4) In ancillary setup mode, under AT Setup/Auto Reset Setup, set AT, and
press the MODE key to begin AT.
1) In Step 1 - Initialization, set the necessary values in auxiliary function
setup mode 2.
2) In Step 2 - Calibration, set the necessary values in ancillary setup mode.
3) In Step 4 - Operation Setup, set the SV (target) value in main setup
mode, and begin control.
4) In ancillary setup mode, under AT Setup/Auto Reset Setup, set AT, and
press the MODE key to begin AT.
See the flowchart below for the operation sequence.
Press for about 1 second.
Press .
Press while holding down .
[Main Setup Mode]
[Ancillary Setup Mode]
Press for about 3 seconds while holding down .
[Auxiliary Function Setup Mode 1]
Press .
PV/SV Display
Control output off function or
auto/manual control function
auto/manual control function
Return to PV/SV Display
SV (target value setting)
AT Setting/
Auto Reset Setting
OUT1
Proportional Band
Setting Lock Selection
SV Max Setting
Sensor Calibration Setting
SV Min Setting
Select Communication Protocol
Select Communication Speed
Set Device Number
Select Parity
Select Stop Bit
Setting
About the Key
The symbol [ ] means
press the key to save
the setting, and proceed to
the next setup item.
The symbol [ ] means
press the key to save
the setting, and proceed to
the next setup item.
Output Operation
Volume Display
Press for about 3 seconds.
• If AT is cancelled, PID returns to the value it
had before AT was run.
• Auto reset is released after about 4 minutes.
• Set the value using the and keys.
• Set 0, 0.0 for ON/OFF operation.
• Set 0, 0.0 for ON/OFF operation.
• Set the value using the and keys.
• Set the value using the and keys.
• Select the communication protocol using the
and keys.
and keys.
• Set the device number using the and
keys.
keys.
• Select the parity using the and
keys.
• Select the stop bit using the and
keys.
• Select the communication speed using the
and keys.
and keys.
• Set the value using the and keys.
• Make a selection using the and
keys.
• AT and auto reset will not function if lock 1/2
specified.
OUT2
Proportional Band
Integral Time Setting
Derivative Time
Setting
OUT1 Proportional
Frequency Setting
OUT2 Proportional
Frequency Setting
A1 Setting
A2 Setting
Heater Cutoff Alarm
ARW Setting
• Set the value using the and keys.
• Displayed if heating/cooling control (OUT2)
• Displayed if heating/cooling control (OUT2)
is added.
• Set the value using the and keys.
• Set to 0 for PD operation, enabling auto
• Set to 0 for PD operation, enabling auto
reset.
• Set the value using the and keys.
• Derivative operation will not function if set to
• Derivative operation will not function if set to
0.
• Set the value using the and keys.
• Displayed during PID operation.
• Displayed during PID operation.
• Set the value using the and keys.
• Not displayed when OUT1 is in ON/OFF
• Not displayed when OUT1 is in ON/OFF
operation, or when output is direct current.
• Set the value using the and keys.
• Not displayed when OUT2 is in ON/OFF
• Not displayed when OUT2 is in ON/OFF
operation.
• Set the value using the and keys.
• Not displayed when [A1 Operation Selection]
• Not displayed when [A1 Operation Selection]
is [ ].
• Set the value using the and keys.
• Not displayed when [A2 Operation Selection]
• Not displayed when [A2 Operation Selection]
is [ ].
• Set the value using the and keys.
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Return to PV/SV Display
Return to PV/SV Display
Notes 1. Sample Alarm 1 (A1) Setup Procedure (Settings marked
1
,
2
,
3
,
4
, and
5
on flowchart).
1
: Under [A1 Operation Selection], select the alarm
operation. (If a value other than [ ] is selected,
items (2) to (5) are displayed. Set them as
necessary.)
items (2) to (5) are displayed. Set them as
necessary.)
2
: Under [A1 Operation Energized/Non-energized
Selection], select Alarm 1 contact output ON
(energized: ), OFF (non-energized: ).
(energized: ), OFF (non-energized: ).
3
: Under [A1 Operation Gap Setting], set the Alarm 1
operation gap.
4
: Set [A1 Operation Delay Timer Setting] (After input
enters alarm operation range, the alarm behavior will
take effect if the setup times out.
take effect if the setup times out.
5
: Under [A1 Setting], set the A1 output operation point.
2. See the user’s manual for information on KT 7, 8, and 9.
3. See the user’s manual for details on factory settings.
3. See the user’s manual for details on factory settings.
Selection
Setting
Setting
Setting
Setting
Setting
Setting
Setting
Setting