LOGO! installation and wiring
2.3 Wiring LOGO!
LOGO!
Manual, 06/2014, A5E33039675
Manual, 06/2014, A5E33039675
37
2.2.4
Labeling LOGO!
The rectangular areas on the LOGO! modules are intended for labeling.
In the case of expansion modules, you can use the rectangular areas for labeling the inputs
and outputs, for example. In this connection, you can enter a delta factor of +8 for the inputs
or +4 for the outputs if the LOGO! Base Module already has 8 inputs or 4 outputs.
2.3
Wiring LOGO!
Wire LOGO! using a screwdriver with a 3 mm blade.
You do not need to wire ferrules for the terminals. You can use conductors fulfilled the
You do not need to wire ferrules for the terminals. You can use conductors fulfilled the
following requirements:
● Cross-sections of up to the following thicknesses:
● Cross-sections of up to the following thicknesses:
– 1 × 2.5 mm
2
– 2 × 1.5 mm
2
for each second terminal chamber
● Conductor material: Cu
● Insulation temperature rating: 75 °C
Tightening torque: 0.5 Nm to 0.6 Nm or 4.5 in-lbf to 5.3 in-lbf.
● Insulation temperature rating: 75 °C
Tightening torque: 0.5 Nm to 0.6 Nm or 4.5 in-lbf to 5.3 in-lbf.
Note
Always cover the terminals after you have completed the installation. To protect LOGO!
Always cover the terminals after you have completed the installation. To protect LOGO!
adequately from impermissible contact to live parts, comply with local standards.
2.3.1
Connecting the power supply
The 230 V versions of LOGO! are suitable for operation with rated voltages of 115 VAC/VDC
and 240 VAC/VDC. The LOGO! 24 V and 12 V versions can be operated with a 24 VDC,
24 VAC or 12 VDC power supply. For information on permissible voltage tolerances, line
frequencies and power consumption, refer to the installation instructions in the Product
Information supplied with your device and to the technical data in Appendix A.