1.4 Sequence of Operation
Operational State
User Interface Display
Explanation
If flame detected before Gas Valve 
opens  during ignition boiler will 
lockout.
Please refer to troubleshooting guide.
Gas Valve energized to deliver air/fuel 
to burner.
If flame undetected after 3 seconds 
boiler will de-energize Gas Valve and 
enter post purge mode for 30 seconds.
Ignition attempted 5 times before 
lockout.
Boiler will run provided all operational 
and safety devices are within limits
Refer to for more information.
Control module adjusts firing rate 
according to heating demand.  When 
Boiler detects demand met, will enter 
post purge mode then standby mode.
  
If simultaneous demand for Central 
Heat and DHW, boiler will enter DHW 
Priority Mode.
Priority mode limits amount of time 
boiler can run in DHW mode to meet 
CH demand.
Max DHW Priority Time setting 
determines maximum time allowed for 
DHW heating mode.
Please refer to section Appendix A 
section 1.5 for more information.
Flame
Detected?
Gas Valve
Energized
Flame 
Detected?
Heat Demand
Met?
DHW 
Priority 
Mode
Simultaneous 
DHW + CH
Demand?
No
Yes
No
Yes
See Max DHW 
Priority Time 
Setting
No
After 2 seconds
After 3 seconds
No
30 second  
post purge
Yes
Yes
Lockout 
Error A21
Note:
5 Ignition 
trials, 
then 
Lockout A01
APPENDIX A - CONTROL MODULE