Site requirements 12
Utilities
Consider the proximity to required utilities, such as power, water, and network connections. While the
required utilities can be brought to nearly any selected site, there is the potential for increased costs and
required utilities can be brought to nearly any selected site, there is the potential for increased costs and
decreased efficiency when the HP POD 20c is located farther from the utility sources.
For utility clearance information, see "Dimensions and clearances (on page
For utility clearance information, see "Dimensions and clearances (on page
)."
Humidifier water supply
The HP POD 20c requires supply water for the humidifier. The supply water must meet the following
requirements.
Requirement
Specification
Pressure
Between 20 and 110 psi, 0.1 and 0.8 MPa
Temperature
Between 1º and 40°C (33º and 104°F)
Minimum flow rate
1.45 lpm (0.12 gpm)
Connection
1.9 cm (.75 in) G
Adapter to 1.9 cm (.75 in) FPS
Adapter to 1.9 cm (.75 in) FPS
Hardness
No greater than 40°fH (equal to 400 ppm of CaCO
3
)
Conductivity
100 to 1250 μS/cm
Organic compounds
None
Type of water
Drinking water. Do not use de-mineralized or softened water.
Instant water fill flow
rate
rate
0.6 lpm (0.16 gpm)
Humidifier
For the exact requirements, see the humidifier documentation.
IMPORTANT:
If your water is out of range, consult a water quality expert.
In addition to the previous requirements, observe the following requirements and recommendations:
•
Do not treat the water with softeners. Softeners can produce foam, which affects the operation of the
unit.
•
Do not use well water, industrial water, water from cooling circuits, or water contaminated by any
chemicals or bacteria.
•
Do not add potential irritants to the water, such as disinfectants or anti-corrosive compounds.
•
The manufacturer recommends installing an in-line filter for the water supply. It is your responsibility to
determine if a filter should be installed, and if so, its location. The filter cannot be installed inside the HP
determine if a filter should be installed, and if so, its location. The filter cannot be installed inside the HP
POD 20c and must be compatible with the type of humidifier that is installed.
For more information, see the Operations and Maintenance Manual or the HP Performance Optimized
Datacenter 20c Maintenance and Service Guide.
Datacenter 20c Maintenance and Service Guide.
Drainage
Requirement
Location
Specification
Condensate drains
Hot aisle side (2)
3.18 cm (1.25 in) drain line and 26.5 lpm (7 gpm) max
Chill Water Header drains Cold aisle side (2)
3.18 cm (1.25 in) drain line and 26.5 lpm (7 gpm) max