DCM-2 SERIAL INTERFACE
 
Commands
Note:  For specific information on the following functions, see the HART interface section of the manual.
Command
torqconst n
torqenable n
Description
Assigns the count value to be 
associated with the torque span.  This 
number is unique to each drive.
Enables or disables the torque 
measurement feature of the drive.
Argument n and Information
n
 = the torque span value in counts.  
This number is determined during 
manufacture and is noted on a tag 
affixed to the drive body within the 
electronics compartment.
n
 = "0" (disabled) or "1" (enabled).
Torque Sensing Commands (con't)
Command
signals
stat
tempf
torq
Description
Displays the present Position signal 
of the drive in volts and the Demand 
signal in milliamps. 
Displays information on the status of 
the drive, including:
  Time / Date
  Demand (% and settings)
  Position (% / inches)
  Error (%)
  Stepsize (inches / %)
  Deadband (inches / %)
  Motor Status
  Run Time
  Line Frequency
  Starts (ext./ret./total)
  Reversals/Stalls
  Overloads
  Positive & Negative Peak Load (%)
  Positive & Negative Peak Torque 
    (% /  inches) 
  Extend and Retract Inhibit Setting
  Alarms
Displays measured temperatures in the 
drive (°F.):
  Low extreme 
  Present temperature
  High extreme
Displays the drive's present torque 
measurement as a percentage of rated 
torque.
Argument n and Information
No argument.
No argument.
No argument.
No argument.
Diagnostic and Information Commands