Beck, R&J ELECTRIC ACTUATORS FOR INDUSTRIAL PROCESSCONTROL 11-1_9 用户手册

下载
页码 88
73
DCM-2 SERIAL INTERFACE
 
Command Error Codes
 Code
  2
  3
  4
  5
  6
  9
 10
 14
 32
 64
Description
Invalid selection
Value too big
Value too small
Data length error
General error
Process too high
Process too low
Span too small
Busy
Not implemented
Information
Displayed when an unknown command 
has been entered.
Displayed when an entered numeric 
value exceeds expected parameters.
Displayed when an entered numeric 
value is less than expected parameters.
Displayed when the wrong number of 
arguments is entered.
Displayed when a combination of 
circumstances prevents a better 
description of the error.
Displayed when the entered value 
exceeds acceptable parameters when 
calibrating a 0% value. 
Displayed when the entered value is 
less than acceptable parameters when 
calibrating a 100% value.
Displayed when entered values for a 0% 
point and a 100% point are too close.
Displayed when a memory store is 
requested and another memory store is 
already in process.
Displayed when an entered command is 
defined, but cannot be implemented.
Command Error Codes
 
When an error is encountered using the serial commands, an "ERROR XX" message is returned.  The 
table below provides a description of the error codes ("XX").