WARNING
Fire hazard. Do not install boiler on combustible 
flooring or carpeting. Failure to follow these 
instructions could result in death or serious injury.
!
   
FOR INSTALLATION ON NON-COMBUSTIBLE FLOORS ONLY 
Boiler must not be installed on carpeting or vinyl flooring. 
Minimum clearances to combustible construction are:
TOP
24 IN.
FRONT
24 IN.
FLUE CONNECTOR
9 IN.
REAR
24 IN.
LEFT SIDE
6 IN.
RIGHT SIDE
24IN.
 
NOTE: Clearance for access should exceed fire protection 
clearance.
• Installations shall conform to the requirements of 
the authority having jurisdiction. Such applicable 
requirements take precedence over the general 
instructions of this manual.
• Where required by the authority having jurisdiction, 
the installation must conform to the American Society 
of Mechanical Engineers Safety Code for Controls and 
Safety Devices for Automatically Fired Boilers, ANSI/
ASME No. CSD-1.
• Locate boiler in front of final position before removing 
crate. 
• Provide level solid base as near chimney as possible 
and centrally located with respect to heat distribution 
system as practical. 
• Allow 24 inches in front, top and right hand side for 
servicing and cleaning, or removing tankless water 
heating coil.
• Recommend 24 inches be allowed in back of boiler for 
convenience when skimming hole is used.
• When installed in a utility room, the door should be 
wide enough to allow largest boiler part to enter, or to 
permit replacement of another appliance such as water 
heater.
• Install boiler such that oil ignition system components 
are protected from water (dripping, spraying, rain etc.) 
during appliance operation and service.
6"
24"
24"
BOILER
24"
Figure #2 - Minimum Clearances To Combustible 
Construction (as seen from above)