•  Adjust gas input to boiler by removing protective cap on 
pressure regulator
and turning screw clockwise 
 to 
increase input and counterclockwise 
 to decrease 
input. 
•  Manifold pressures are taken at outlet side of gas 
valve. 
•  To check for proper flow of natural gas to boiler, divide 
input rate shown on rating plate by heating value of 
gas obtained from local gas company. This determines 
number of cubic feet of gas required per hour. 
•  With all other gas appliances off, determine flow of gas 
through meter for two minutes and multiply by 30 to 
get hourly rate. 
•  Make minor adjustments to gas input as described 
above. See Figure 16 page 18.
•  Change burner orifices if final manifold pressure 
varies more than plus or minus 0.3 inches water 
column from specified pressure listed on boiler 
rating plate. 
•  Primary air adjustment is not necessary, therefore 
air shutters are not furnished as standard 
equipment. 
CHECK SAFETY CONTROL CIRCUIT.  Test ignition 
system safety shutoff device after placing boiler in 
operation. Figure 15 page 19.
1. 
Intermittent Pilot: With main burner operating, turn 
pilot gas adjusting screw clockwise 
 until pilot 
gas is turned off. Within 90 seconds main gas control 
closes, shutting off gas to main burner.
2. 
High Limit Control: Remove plastic cover and 
note temperature setting. Refer to appendix A for 
adjustment procedure. Decrease setting to minimum 
and operate boiler. When boiler water temperature 
exceeds control temperature setting, control will open 
circuit, closing automatic main gas valve. Figure 21.
14 - CHECKING GAS INPUT RATE TO BOILER
Figure 21 - High Limit Control Location
Burner Access 
Door
Gas Valve
High Limit and 
Operating Control