Utica Boilers MGB Series II/MGC Series 安装指导

下载
页码 28
23
APPENDIX A - CONTROL MODULE
A.1 Installation Environment Considerations
 WARNING
If you do not follow these instructions 
exactly, a fire or explosion may result 
causing property damage, personal injury 
or loss of life.
• Do not use this appliance if any part has 
been under water. Immediately call a qualified 
service technician to inspect appliance and to 
replace any part of control system and any gas 
control which has been under water.
• Do not allow water to drip on controls. Prevent 
condensation by allowing air circulation around 
module and gas control. 
• Do not use corrosive chemicals around or on 
module or gas control.
!
  
• Controls can be damaged by excessively high 
temperatures.  Verify adequate air circulation around 
control is maintained when installing boiler.
A.2 Electrical Connections
Connect Module Connectors Figure 13, Page 16
• Connect L1& L2 leads inside J-box using wire nuts. 
Secure J-box cover.
• Connect Circulator harness to circulator. Harness 
comes plugged into module with Molex
®
 plug.
• Connect thermostat connection to yellow wires 
marked TT using wire nuts.
• Ensure remaining Molex
®
 plug connectors have not 
worked loose during transit.
• Check sensing bulb is fully inserted in well and is not 
loose. 
A.3 Adjusting Settings
To discourage unauthorized changing of settings, procedure 
to enter adjustment mode is required. 
To enter adjustment mode, press UP, DOWN, and I buttons 
simultaneously for three seconds. Press and release I 
button until parameter requiring adjustment is displayed. 
See Figure 12, page 16.
 
о “SP_”   Setpoint (180 °F default setting; adjustable 
between 130 and 220 °F). Note: on some models 
this is "HL" High Limit.
 
о “Df_”   Setpoint Differential (15 °F default setting; 
adjustable between 10 and 30 °F)
 
о “°F_”  Degrees Fahrenheit
Press UP or DOWN button until parameter has reached 
desired value. After 60 seconds without any button inputs, 
control automatically returns to READ mode.
A.4 Display
In RUN mode, status items and parameters are viewable. 
Example, to display setpoint, control flashs “sp” (setpoint) 
followed by temperature (i.e., 135), followed by °F or °C.
To read settings, press and release I key to find parameter 
of interest. 
Example, press and release I until setpoint (sp) is 
displayed, followed by three-digit number, i.e., 190, 
followed by °F or °C. Press I button again will display (S1T) 
Sensor 1 Temperature followed by three-digit number and 
corresponding degree designator. 
See Display Readout.
Figure 22 - Display Readout