5 - VENTILATION & COMBUSTION AIR
Provide combustion air and ventilation air in accordance 
with the section “Air for Combustion and Ventilation,” 
of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or 
applicable provisions of local building codes.
Provide make-up air where exhaust fans, clothes 
dryers, and kitchen ventilation equipment interfere 
with proper operation.
National Fuel Gas Code recognizes several methods 
of obtaining adequate ventilation and combustion air.  
Requirements of the authority having jurisdiction may 
override these methods.
• Engineered Installations.  Must be approved by 
authority having jurisdiction.
• Mechanical Air Supply.  Provide minimum of 
0.35 cfm per Mbh for all appliances located 
within space.  Additional requirements where 
exhaust fans installed.  Interlock each appliance 
to mechanical air supply system to prevent main 
burner operation when mechanical air supply 
system not operating.
• All Indoor Air.  Calculate minimum allowable room 
volume for all appliances in space.  Use a different 
method if minimum volume not available.
A.  Standard Method.  Cannot be used if known 
air infiltration rate is less than 0.40 air 
changes per hour.  See Table 4 for space 
with boiler only.  Use equation for multiple 
appliances.
Volume ≥ 50 ft
3
 x Total Input [Mbh]
B.  Known Air Infiltration Rate.  See Table 4 
for space with boiler only.  Use equation 
for multiple appliances.  Do not use an air 
infiltration rate (ACH) greater than 0.60.
Volume ≥
 
21 ft
3
⁄ACH x Total Input [Mbh]       
C.  Refer to National Fuel Gas Code for opening 
requirements between connected indoor 
spaces.
• All Outdoor Air.  Provide permanent opening(s) 
communicating directly or by ducts with outdoors.
A.  Two Permanent Opening Method.  Provide 
opening commencing within 12 inches of top 
and second opening commencing within 12 
inches of bottom of enclosure.
 
…
Direct communication with outdoors or 
communicating through vertical ducts. 
Provide minimum free area of 1 in² per 4 
Mbh of total input rating of all appliances 
in enclosure.
 
…
Communicating through horizontal ducts.  
Provide minimum free area of 1 in² per 2 
Mbh of total input rating of all appliances 
in enclosure.
B.  One Permanent Opening Method.  Provide 
opening commencing within 12 inches of top 
of enclosure.  Provide minimum clearance of 
1 inch on sides/back and 6 inches on front 
of boiler (does not supersede clearance to 
combustible materials).
•  Refer to National Fuel Gas Code for additional 
requirements for louvers, grilles, screens and air 
ducts.
• Combination Indoor and Outdoor Air. Refer 
to National Fuel Gas Code for application 
information.
Table 4 - Minimum Room Volume, Indoor Air Only*
Room Cubic Feet Volume
Input 
Mbh
Standard 
Method
Known Air Infiltration Rate Method (Air Changes Per Hour)
0.1
0.2
0.3
0.4
0.5
0.6
262.5
13125
55125
27563
18375
13781
11025
9188
299
14950
62790
31395
20930
15698
12558
10465
* Table values based on boiler only. Add volume for any additional appliances.