Gas Supply Connection, Natural Gas Only
1. 
Use piping materials and joining methods acceptable 
to authority having jurisdiction.  In absence of such 
requirements USA - National Fuel Gas Code, ANSI 
Z223.1/NFPA 54 
2. 
On multiple base boilers, connect gas service with 
branch lines from common main.  
3. 
Install ground joint union in each branch line for easy 
servicing of gas controls. 
4. 
Provide sediment trap up stream of gas valve. Figure 36
5. 
Size and install gas piping system to provide sufficient 
gas supply to meet maximum input at not less than 
minimum supply pressure. See Chart 6 for pipe sizes 
for gas mains.
6. 
Pressure test boiler and gas connection before 
placing boiler in operation.
• Pressure test over 1/2 psig (3.5 kPa).  Disconnect 
boiler and its individual gas shutoff valve from 
gas supply system.
• Pressure test at 1/2 psig (3.5 kPa) or less.  
Isolate boiler from gas supply system by closing 
manual gas shutoff valve. 
• Locate leakage using gas detector, noncorrosive 
detection fluid, or other leak detection method 
acceptable to authority having jurisdiction.  Do 
not use matches, candles, open flames, or other 
methods that can provide ignition source.
• Correct leaks immediately and retest.
Chart 5
Minimum Operating Gas Supply Pressure
Models
5.0 inches w.c.
300
 500
600
1000 1300 1500
Models
5.3 inches w.c.
400
700
800
900
1100 1200 1400
All 
Models
Maximum Gas Supply Pressure
13.5 inches w.c.
All 
Models
Manifold Pressure
3.5 inches w.c.
Chart 6
TABLE OF PIPE SIZES IN INCHES FOR GAS MAINS 
(NATURAL GAS)
Boiler 
No
20’ 30’ 40’ 50’ 60’ 80’ 100’ 125’ 150’
300
1¼ 1¼ 1¼ 1¼ 1¼ 1¼
400
1¼ 1¼ 1¼ 1¼ 1½ 1½
2
500
1¼ 1¼ 1¼ 1½ 1½ 1½
2
2
2
600
1¼ 1½ 1½ 1½
2
2
2
2
2
700
1¼ 1½ 1½
2
2
2
2
2
800
1½ 1½
2
2
2
2
2
900
2
2
2
2
2
1000
2
2
2
2
1100
2
2
2
2
2
1200
2
2
2
2
2½ 2½
3
1300
2
2
2
2½ 2½ 2½
3
3
1400
2
2
2
2½ 2½ 2½
3
3
3
1500
2
2
2½ 2½ 2½ 2½
3
3
3
CONNECTING GAS SERVICE
Figure 36
CAUTION
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use 
any phone in your building.
• Immediately call your gas supplier from a 
neighbor’s phone.  Follow gas supplier’s 
instructions. 
• If you cannot reach your gas supplier, call the fire 
department.
!
  
DANGER
Fire Hazard.  Do not use matches, candles, open 
flames, or other methods providing ignition source. 
Failure to comply will result in death or serious 
injury.
!