Utica Boilers JE 安装指导
29
Electrical Wiring
1.
Electrically bond boiler to ground in accordance with
requirements of authority having jurisdiction. Refer to
National Electrical Code, ANSI/NFPA 70.
2.
Install fused disconnect switch between boiler and
electrical panel in convenient location.
3.
Secure wiring from high temperature limit control to boiler
jacket or gas piping to prevent accidental disconnect from
controls.
4.
Tape all wiring to gas valves securely to gas supply lines
or run in appropriate conduit.
Thermostat Installation
1.
Follow instructions included with your thermostat.
2.
Locate thermostat about 5 feet above floor on inside wall.
3.
Keep thermostat(s) at desired room temperature.
If windows are opened or heat is not needed, set
thermostat(s) to lower setting.
Adjust Thermostat Heat Anticipator
1.
Set heat anticipator setting per thermostat
manufacture instructions.
2.
Follow thermostat manufacture instructions for final
adjustment.
3.
When set above temperature indicated on
thermometer, boiler burners should ignite. Verify
thermostat(s) turns boiler off when room temperature
reaches selected setting and starts boiler when room
temperature falls few degrees.
4.
Set thermostat for desired temperature.
MULTIPLE
BASE BOILERS
5.
PLACES TO AVOID LOCATING THERMOSTAT
Dead Spots
Behind Doors
Corners and Alcoves
Corners and Alcoves
Hot Spots
Concealed Pipes
Fireplaces
TV Sets
Lamps
Direct Sunlight
Kitchens
Fireplaces
TV Sets
Lamps
Direct Sunlight
Kitchens
Cold Spots
Concealed Pipes or Ducts
Stairwells
Drafts
Unheated Rooms on other side of Wall
Stairwells
Drafts
Unheated Rooms on other side of Wall
ELECTRICAL WIRING
CAUTION
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and
dangerous operation.
!
WARNING
Electrical shock hazard. Turn OFF electrical power
supply at service panel before making any line
voltage connections. Failure to do so could result
in death or serious injury.
!