Utica Boilers JE 安装指导

下载
页码 36
8
COMBUSTION AIR REQUIREMENTS – 
Chart #3
(MINIMUM SQUARE INCHES OPENING)
MODEL
NUMBER
BOILER
MODULES
*UNCONFINED AREA
**CONFINED AREA
OUTSIDE COMBUSTION AIR
OUTSIDE
COMBUSTION
AIR 1 SQ. IN
/4000 Btu/hr
(SEE FIG. 2)
INSIDE
COMBUSTION
AIR 1 SQ. IN.
/1000 Btu/hr
(SEE FIG. 1)
VERT. DUCTS
1 SQ. IN.
/4000 Btu/hr
HORZ. 
DUCTS
1 SQ. IN.
/2000 Btu/
hr
 300
1
75
300
75
150
400
1
100
400
100
200
 500
1
125
500
125
250
600
2
150
600
150
300
700
2
175
700
175
350
800
2
200
800
200
400
900
2
225
900
225
450
1000
2
250
1000
250
500
1100
3
275
1100
275
550
1200
3
300
1200
300
600
1300
3
325
1300
325
650
1400
3
350
1400
350
700
1500
3
375
1500
375
750
* Unconfined area: A space whose volume  is not less than 50 cubic feet per 1000 Btu 
per hour of all appliances installed in that space (cubic feet of space = height x width 
x length).
** Confined area: A space whose volume is less than 50 cubic feet per 1000 Btu per 
hour of all appliances installed in that space (cubic feet of space = height x width x 
length).
VENTILATION  AND COMBUSTION AIR
 WARNING
Air openings to combustion area shall not be 
obstructed. Follow Chart 3 to insure adequate 
combustion air is maintained.
!
  
 WARNING
Asphyxiation hazard. Ensure enough air is available 
for proper combustion, avoiding hazard due to lack 
of oxygen.  
!