RuggedCom Welder RS400 用户手册

下载
页码 275
Serial Protocols 
 
 
ROS™  v3.5 
78 
RS400 
TIN Mode: 
Synopsis: 1 to 2 
Default: 1 
TIN Protocol running mode.  
TIN Transport: 
Synopsis: { TCP, UDP } 
Default: UDP 
The network transport used to transport protocol data over IP network. 
WIN Transport: 
Synopsis: { TCP, UDP } 
Default: UDP 
The network transport used to transport protocol data over IP network. 
TIN IP Port 
Synopsis: 1024 to 65535 
Default: 51000 
The local port number on which TIN protocol listens for TCP connections or UDP datagrams. 
WIN IP Port 
Synopsis: 1024 to 65535 
Default: 52000 
The local port number on which WIN protocol listens for TCP connections or UDP datagrams. 
Message Aging Timer 
Synopsis: 1 to 3600 or { Disabled } 
Default: Disabled 
This timing parameter (in seconds) is used to configure the removal of duplicate messages in 
TIN mode2. If the same message is received within the time interval specified by this parameter, 
the new message is considered duplicate, and is thus discarded. 
Address Aging Timer 
Synopsis: 60 to 1000 
Default: 300 s 
The time of communication inactivity after which a learned TIN address is removed from the 
device address table. Entries in Link Statistics Table with the aged address will be kept until 
statistics are cleared. 
Broadcast Addresses 
Synopsis: { Static, Dynamic, StaticAndDynamic } 
Default: Static 
A The device address table in which addresses will be found for broadcast messages. 
Unicast Addresses 
Synopsis: { Static, Dynamic, StaticAndDynamic } 
Default: Dynamic 
A The device address table in which addresses will be found for unicast messages. 
Link Stats 
Synopsis: { Disabled, Enabled } 
Default: Enabled 
Enables links statistics collection for protocol.