Section 4
Exploring Basic Test Operations
Now that your DM-2A mark II gauge and fan are properly connected you’re ready to begin 
taking measurements. A good place to start is to conduct a simple pressure-pressure test. Doing 
this, you’ll learn how to turn on the gauge, choose a Mode, activate Time Average and Auto Zero 
features, and control fan speed and pressure using Set SpeedSet Pressure, and Jog/Hold.
Follow these steps as a practical example:
1.  With your DM-2A mark II gauge and testing device properly connected, turn on 
your gauge by pressing the O
n
/O
ff
 keypad button once to display the Retrotec 
introduction screen and press any keypad button to proceed to the main operational 
screen. 
  The procedure involved in each of the following steps applies to a typically configured 
gauge. If your gauge has been configured differently, the specific information discussed in 
these steps may differ from your current setup. 
Setting the Mode
2.  Press the M
Ode
 keypad button to cycle through the enabled modes until the display 
screen indicates two pressure readings—PrA and PrB (as shown next). Notice the 
pressure readings on the gauge fluctuate slightly. This is due to minute pressure 
changes in the room or enclosure that the gauge is currently measuring. Since the 
DM-2A mark II takes pressure readings 20 times per second, the readings can change 
rapidly.
DM-2A Mark II Dual-Channel Pressure Gauge 
User Manual
4:
 
Basic Operations