To perform your CGSB 149.10 standards test procedure, follow these steps:
1.  Assess and measure the Envelope Area as specified in the standard.
2.  With your gauge on and running and from the main operation screen, press the 
M
Ode
 keypad button to set your gauge to EqLA/Area mode.
  For the EqLA/Area mode to be available, it must be enabled. To enable a mode use options 
in the Setup screen. A mode is enabled when it is set to a value other than off.
3.  Press the e
nteR
 keypad button and input the envelope area value according to 
your measurements.
4.  Conduct door-fan test at 50 Pa or as specified in the standard.
5.  Use the @ p
ReSSuRe
 keypad button to display the Flow @ 25.0 Pa and the EqLA @ 
10.0 Pa.
6.  Results for EqLA and NLA (=EqLA/Area) may be read directly from your gauge.
7.  Your CGSB 149.10 standards test procedure is complete.
  For more information on standards used by the Canadian General Standards Board, visit 
http://pwgsc.gc.ca/cgsb/home/index-e.html
Canadian ecoENERGY Configuration
The Canadian ecoENERGY Program requires reading of EqLA at 10 Pa and air-changes at 50 Pa. 
Most test technicians prefer using imperial units but metric units are simply to apply. Your DM-
2A gauge will provide these values automatically without doing a multipoint test or you can 
use Retrotec’s Door-Fan 3.0 software to perform the test manually or even automatically with 
Retrotec model Q systems such as the Q46, Q4E and Q56. 