Retrotech DM-2A 用户手册

下载
页码 60
40
Retrotec Energy Innovations, Ltd.
DM-2A Mark II   2008-02-22
DS/EN 13829
To configure your gauge for the Dansk Standard for thermal performance of buildings, 
determination of air permeability of buildings, fan pressurization method, apply the following 
settings:
DS/EN 13829 Configuration
Mode Setup
Pressure
Pa
Flow
m
3
/h
@ 50.0 Pa
EfLA
Off
EqLA
Off
Air Changes
/h
@ 50.0 Pa
Flow per Area
cm
3
/h/m
2
@ 50.0 Pa
EqLA per Area
Off
Velocity
Off
Velocity Flow
Off
(Other Settings)
n
0.65
Power Down Hour
2
Area
m
2
Volume
m
3
European
No
Sig Figs
2.5
Reverse Mode
No
DS/EN 13829 is a multi-point test. However, the DM-2A mark II can also provide for 
quick single-point checks of the enclosure. To perform a single-point test, follow these 
steps:
1.  Assess and measure the Envelope Area as specified in the standard.
2.  Assess and measure the Net Floor Area as specified in the standard.
3.  Assess and measure the Internal Volume of the building as specified in the standard.
4.  With your gauge on and running and from the main operation screen, press the M
Ode
 
keypad button to set your gauge to the Air Chg mode.
5.  Press the e
nteR
 keypad button and input the Internal Volume as measured in step 3.
6.  Press the M
Ode
 keypad button to display screen to view the Flow/Area mode.
DM-2A Mark II Dual-Channel Pressure Gauge 
User Manual
A:
 
Specific Configurations