Omron SYSMAC C200HW-ZW3AT2-E-V2 用户手册

下载
页码 182
5-3
Section
L: Data Link
61
To cancel the initialization processing, press “N” and then the Enter Key.
5-3-7 Checking Data Link Tables — K: Check Table
“K: Check table” is used to check data link tables for errors or inconsistencies. It
can also check for inconsistencies between the data link tables for multiple
nodes.
If errors are detected, correct the data link tables as described in Error Mes-
sages 
(on page 63).
Note
1) Before executing “K: Check table,” always select “I: Device Info Set” from
the Data Link Menu and specify the PC models.
2) “K: Check table” checks the data link tables in the computer memory. To
check the data link table that has been set for a node, use “T: Transfer table”
on the Data Link Menu to read the table to the computer, then execute
“K: Check table.”
1, 2, 3...
1. Select “K: Check table” from the Data Link Menu. If the number of nodes set
in all data link tables is 0, an error message will be displayed.
The following window will be displayed to prompt you to specify the check
level.
2. Select the error level to be checked. The following window will be displayed
to prompt you to specify the nodes to be checked.
When the window appears, each node will be displayed as shown as fol-
lows, depending on the number of nodes set in the data link table in the
memory:
Nodes for which the number of nodes is not 0:
YES (checked)
Nodes for which the number of nodes is 0:
No display (not checked)
Error level
Meaning
Rank A (error)
Indicates serious errors.
If this level of error is detected, the data links will not
execute normally.
Rank B (warning)
Indicates minor errors or the locations of settings that
could be faulty.
Even if this level of error is detected, the data links will
execute, but may result in unexpected operation. The
settings should be checked.