Maretron FPM100 用户手册

下载
页码 23
 
 
 
 
 
Revision 1.3 
 
Page 11 
®
®
3.3.2  Configuring Pressure at 4mA 
Program this parameter to match the pressure reading of the pressure transducer when it is 
sourcing a current of 4mA. You can determine this value by examining the specification of the 
pressure transducer being used. 
 
3.3.3  Configuring Pressure at 20mA 
Program this parameter to match the pressure reading of the pressure transducer when it is 
sourcing a current of 20mA. You can determine this value by examining the specification of the 
pressure transducer being used. 
 
3.3.4  Configuring Tank Capacity 
In addition to indicating the fluid level within a tank, the FPM100 also has the ability to be 
configured or programmed with the attached tank’s capacity. This way, you will be able to view 
the tank’s capacity as well as the amount of liquid remaining anywhere on the vessel where 
there is an NMEA 2000
®
 compatible display. It is not required, but you can enter the FPM100 
tank capacity using a display product such as the Maretron DSM250. Refer to the user’s 
manual of the particular product that will be used for configuring the FPM100 as these manuals 
provide detailed instruction on configuration procedures. 
 
3.3.5  Tank Levels Calibration 
The FPM100 can be easily programmed for use with tanks of rectangular cross-section (see 
Section 3.3.5.1). For non-rectangular tank shapes, you can perform custom calibration so that 
the FPM100 accurately reflects fluid levels (see Section 3.3.5.2).  
 
3.3.5.1  Rectangular Tank 
 
3.3.5.1.1 Empty Tank Depth 
This field should be programmed with the depth of the liquid column above the pressure 
transducer when the tank is empty. If the transducer is installed directly in the tank, then this 
value will normally be programmed to 0”. If the transducer is actually installed below the level 
of the tank bottom, then this value should be programmed to the vertical distance between the 
tank bottom and the pressure port on the pressure transducer. 
 
3.3.5.1.2 Full Tank Depth 
This field should be programmed with the depth of the liquid column above the pressure 
transducer when the tank is full. 
 
Please refer to Figure 8 below for an illustration of Full Tank Depth and Empty Tank Depth 
parameters.