Liebert Universal Monitor 用户手册

下载
页码 144
System and Control Options
45
9.2
Setup System - Overview
The Setup System screen displays seven options that allow you to configure input and output 
devices and their relationships, the common alarm, the modem, pagers to be dialed when alarms 
occur, and a variety of system details, such as login password and system date and time:
• Setup Input
• Setup Common Alarm
• Setup Sensor
• Setup  I/O  Matrix
• Setup Output
• Setup Modem & Pagers
• Setup System Info
• Setup Exp Board
9.3
Setup System - Setup Input
The Universal Monitor has eight digital input points that may be 
configured individually. If the optional Expansion Board is used, an 
additional 16 digital inputs may also be configured. These inputs may 
have a wide variety of Liebert or other manufacturers’ equipment 
connected for monitoring.
To configure a digital input:
Log In and Choose Setup System
• From the Main Menu, use the arrows
↑ ↓
 to
 
choose System and 
Control, then press Enter ↵  (see 9.1 - Login for help).
• Enter your password at the Login screen.
• From the System and Control Menu, use the arrows
↑ ↓
 to
 
choose 
Setup System, then press Enter ↵ .
Select a Digital Input to Configure
• From the Setup System Menu, shown at right, use the arrows
↑ ↓
 to
 
choose Setup Input and press Enter ↵ .
• From the Select Input Menu, choose the input you want—for exam-
ple, Input_01—and press Enter ↵ .
Table 21 shows the digital input features you may change, along with 
the default settings: you may change the name of the input, define it as 
normally open or closed, and specify it as alarmable or as an event.
• Alarmable inputs may be defined as either Unlatched or Latched.
• Event status allows you to monitor a digital input’s state—and use a change in state to initiate an 
action through an output, if desired—without triggering an alarm. Events are always Unlatched.
• You may also specify a time delay before the Universal Monitor responds to an alarm or event.
Use the steps following Table 21 to change the default settings for any digital input.
Table 21
Default settings - digital inputs
Feature
Default
Other Options
LABEL
INPUT_01
Any name (up to eight characters)
NORM OPEN/CLOSE
NO (Normally open)
NC (Normally closed)
ALARM/EVENT
AL (Alarmable)
EV (Event)
LATCHED
NL (Unlatched) / N (No)*
L (Latched) / Y (Yes)*
DELAY
00:01 (1 second)
Any time (in minutes and seconds) from 00:00 to 99:59
NOTE: Different abbreviations are used to designate a digital input as Latched or Unlatched as shown below.
Settings - Select Input Menu
(see Section 9.3)
When configuring an input
(see Section 9.3.4)
Unlatched
NL (Not Latched)
N (No, not latched)
Latched
L (Latched)
Y (Yes, latched)
Setup System Menu
> SETUP INPUT
SETUP COMMON ALARM
SETUP SENSOR
SETUP I/O MATRIX
↑ ↓=NEXT
=SELECT
SETUP OUTPUT
SETUP MODEM&PAGERS
SETUP SYSTEM INFO
SETUP EXP BOARD
Select Input Menu
SELECT INPUT
> INPUT_01  NO-AL-NL
INPUT_02  NO-AL-NL
↑ ↓=NEXT
=SELECT
INPUT_03  NO-AL-NL
INPUT_04  NO-AL-NL
INPUT_05  NO-AL-NL
INPUT_06  NO-AL-NL
INPUT_07  NO-AL-NL
INPUT_08  NO-AL-NL
INPUT_09
NO-AL-NL
INPUT_10
NO-AL-NL
INPUT_11
NO-AL-NL
INPUT_12
NO-AL-NL
INPUT_13
NO-AL-NL
INPUT_14
NO-AL-NL
INPUT_15
NO-AL-NL
INPUT_16
NO-AL-NL
INPUT_17
NO-AL-NL
INPUT_18
NO-AL-NL
INPUT_19
NO-AL-NL
INPUT_20
NO-AL-NL
INPUT_21
NO-AL-NL
INPUT_22
NO-AL-NL
INPUT_23
NO-AL-NL
INPUT_24
NO-AL-NL
NOTE: INPUT_09 - INPUT_24
for optional Expansion Board