System and Control Options
46
9.3.1 Change Label (Name of Input)
Each input has a default label (Input_01, Input_02, etc.) that you may 
change to a more descriptive name for ease in recognizing alarms and 
events associated with the input. The label may consist of up to eight 
characters (see Table 20 for valid characters).
• From the Setup Input Menu, choose Label for the selected 
input—Label: Input_01 in the example at right—and press 
Enter ↵ .
• To change the input’s label, which may consist of up to eight char-
acters:
• Use the arrows
↑ ↓
 to
 
choose a character.
• Press Enter ↵  to advance to the next character position.
• When finished, press Enter ↵  again.
9.3.2 Define Input as Normally Open or Normally Closed
Each input may be set up as Normally Open (NO) or Normally Closed 
(NC). The default setting for all input points is NO (Normally Open).
If you require an input to be a supervised point, define the input as 
Normally Closed (NC).
• From the Setup Input Menu, choose Norm Open/Close, as shown 
at right, and press Enter ↵ .
• To change the normal state for this input, use the arrows
↑ ↓
 to
 
choose NO (Normally Open) or NC (Normally Closed), then press 
Enter ↵ .
9.3.3 Define Input as Alarmable or Event
Each digital input may be defined as Alarmable (AL) or as an 
Event (EV).
• For a digital input defined as alarmable, the following alarm reac-
tions occur when the status of the monitored input device changes: 
the LCD flashes, the audible horn sounds, configured pager num-
bers will be notified and a record is entered in the Alarm Log.
• For a digital input defined as an event, the status change is 
recorded in the Event Log.
By default, all digital inputs are set up as AL (Alarmable).
• From the Setup Input Menu, choose Alarm/Event, as shown at 
right, and press Enter ↵ .
• To change the type of digital input, use the arrows
↑ ↓
 to
 
choose 
AL (Alarmable) or EV (Event), then press Enter ↵ .
Setup Input Menu
SETUP INPUT_01
> LABEL: INPUT_01
NORM OPEN/CLOSE: NO
ALARM/EVENT: AL
↑ ↓=NEXT
=SELECT
LATCHED: N
DELAY: 00:01
Change Label
CHANGE LABEL
INPUT_01
↑ ↓=SELECT 
=NEXT/END
Setup Input Menu
SETUP INPUT_01
LABEL: INPUT_01
> NORM OPEN/CLOSE: NO
ALARM/EVENT: AL
↑ ↓=NEXT
=SELECT
LATCHED: N
DELAY: 00:01
Normally Open / Closed
IS INPUT NORMALLY
OPENED OR CLOSED? NO
↑ ↓=NO/NC
=END
Setup Input Menu
SETUP INPUT_01
LABEL: INPUT_01
NORM OPEN/CLOSE: NO
> ALARM/EVENT: AL
↑ ↓=NEXT
=SELECT
LATCHED: N
DELAY: 00:01
Alarmable / Event
IS INPUT AN ALARM
OR EVENT? AL
↑ ↓=AL/EV
=END