Manual Supplement
00809-0500-4530, Rev AA
October 2010
Rosemount 5300/5400 Series
1-26
Table 1-13.  Output Variables for the 
Configurable Floating Point Format 
(default code 1)
The Rosemount 5300/5400 register area starting with register 2000 is used 
for hosts that require Floating Point Format Code 0 (see Table 1-14).
Floating Point Format Codes 2 and 3 use register areas 2100 and 2200, 
respectively (see Table 1-15 and Table 1-16).
Register Name
Register 
Number
Note
Slave 1 Status 
Conf
1300
Bit information in bitfield.
Bit 0: Invalid Measurement Slave 1 PV.
Bit 1: Invalid Measurement Slave 1 Non PV.
Bit 2: Invalid Measurement Slave 1 Non PV.
Bit 3: Invalid Measurement Slave 1 Non PV.
Bit 14: HART bus busy (slave in burst or other 
master present)
Bit 15: HTM Task not running (option not 
available).
Note: Bit 1-3 is set when Invalid Measurement of 
Slave 1 Non PV. i.e. all three bits are set 
simultaneously.
Slave 1 PV Conf
1302
Primary variable from slave 1 represented in 
IEEE 754 format, using the byte order set in the 
FloatingPointFormatCode register.
Slave 1 SV Conf
1304
Secondary variable from slave 1 represented in 
IEEE 754 format, using the byte order set in the 
FloatingPointFormatCode register.
Slave 1 TV Conf
1306
Tertiary variable from slave 1 represented in 
IEEE 754 format, using the byte order set in the 
FloatingPointFormatCode register.
Slave 1 FV Conf
1308
Fourth variable from slave 1 represented in IEEE 
754 format, using the byte order set in the 
FloatingPointFormatCode register.
Slave 2 data
1310-1318
Same data as for Slave 1.
Slave 3 data
1320-1328
Same data as for Slave 1.
Slave 4 data
1330-1338
Same data as for Slave 1.
Slave 5 data
1340-1348
Same data as for Slave 1.