Manual Supplement 
00809-0500-4530, Rev AA
October 2010
1-27
Rosemount 5300/5400 Series
Table 1-14.  Output Variables for 
Floating Point Format Code 0
Table 1-15.  Output Variables for 
Floating Point Format Code 2
Register Name
Register Number
Note
Slave 1 Status
2000
Bit information in bitfield:
Bit 0: Invalid Measurement Slave 1 PV.
Bit 1: Invalid Measurement Slave 1 SV.
Bit 2: Invalid Measurement Slave 1 TV. 
Bit 3: Invalid Measurement Slave 1 FV.
Bit 14: HART bus busy (slave in burst or 
other master present)
Bit 15: HTM Task not running (option not 
available).
Note: Bit 1-3 is set when Invalid 
Measurement of Slave 1 Non PV, i.e. all 
three bits are set simultaneously.
Slave 1 PV 
2002
Primary variable from slave 1 
represented in IEEE 754 format, using 
Floating Point Format Code 0.
Slave 1 SV
2004
Secondary variable from slave 1 
represented in IEEE 754 format, using 
Floating Point Format Code 0.
Slave 1 TV
2006
Tertiary variable from slave 1 
represented in IEEE 754 format, using 
Floating Point Format Code 0.
Slave 1 FV (QV)
2008
Fourth variable from slave 1 represented 
in IEEE 754 format, using Floating Point 
Format Code 0.
Register Name
Register Number
Note
Slave 1 Status
2100
Bit information in bitfield:
Bit 0: Invalid Measurement Slave 1 PV.
Bit 1: Invalid Measurement Slave 1 SV.
Bit 2: Invalid Measurement Slave 1 TV. 
Bit 3: Invalid Measurement Slave 1 FV.
Bit 14: HART bus busy (slave in burst or 
other master present)
Bit 15: HTM Task not running (option not 
available).
Note: Bit 1-3 is set when Invalid 
Measurement of Slave 1 Non PV, i.e. all 
three bits are set simultaneously.
Slave 1 PV 
2102
Primary variable from slave 1 
represented in IEEE 754 format, using 
Floating Point Format Code 2.