Aprilaire Ventilation Hood 8100 用户手册

下载
页码 12
SERVICE
CLEARANCE
12"
12"
36"
37-7/16"
20-9/16"
CEILING MOUNTING HOLES
CEILING MOUNTING HOLES
ON / OFF
SWITCH
WALL
MOUNTING
HOLES
WALL
MOUNTING
HOLES
RETURN
STALE AIR
SUPPLY
FRESH AIR
EXTERNAL CONTROL WIRING ACCESS
6" ROUND COLLARS
12-3/4"
6" ROUND
COLLARS
2"
2"
fIGURE 3 – Dimensions and location Considerations
90-1743
lOCATION CONSIDERATIONS
1 . 
 Install Unit Indoors: It is recommended that the Model 8100 ERV be mounted in a conditioned space . If the unit is mounted in an area where 
the temperature may drop below 32°F or exceed 100°F, 
all duct work in the unconditioned space must be insulated .
2 . 
 Mounting: The recommended mounting location is on the basement foundation wall, or a stud wall with easy access to the HVAC system . 
The unit may also be mounted to basement ceiling joists .
3 . 
 Mounting  Kit: The unit must be mounted with the mounting kit provided .
4 . 
 power: Outlet within 30” of unit .
5 . 
 Service  Clearances: Allow a minimum of 36” clearance around the access door . Allow for 12” of clearance to access duct connections, on/
off switch and wiring connections . (See 
figure 3 .)
3