Analog outputs automatically set the output voltages to 0 V if too much time elapses 
after the last Poll Command message received by the device. At this timeout 
condition, the output of the generator shuts off and goes safe.
DEVICENET ROTARY SWITCHES: BAUD RATE AND ADDRESSING
The DeviceNet interface features three rotary switches, located on the rear, which are 
read each time the DeviceNet interface powers up. Use the Data Rate switch to select 
a baud rate: 125, 250, or 500 kbaud (0 = 125;1 = 250; 2 = 500 kbaud). The default is 
500 kbaud. A switch setting in the PGM region lets you configure the baud rate 
through DeviceNet.
The signals available at the RS-232, AE Bus Host port conform to the RS-232 
interface standards. Each generator is factory preset for a baud rate of 19.2 kb and 
Address 1. Table 4-4 describes the RS-232, AE Bus Host pin signals.
Figure 4-10. DeviceNet control panel
Use the MSD and LSD switches to select the unit’s address (MAC ID). MAC IDs 0 
through 63 are valid. Use the MSD switch to select the MAC ID’s most significant 
digit; use the LSD switch to select the MAC ID’s least significant digit. Switch 
settings greater than 63 (or in the “PGM” region of the MSD switch) let you configure 
the MAC ID through DeviceNet.
DEVICENET CONTROL PANEL LEDS
The rear panel of the Apex generator features two, bi-color LEDs (see Figure 4-20). 
One is labeled MOD and indicates module status. The other is labeled NET and 
indicates network status.
Devicenet Module Status LED
The MOD bi-color (amber/green) LED provides device status. It indicates whether the 
device has power and is operating properly. Table 4-14 shows the LED’s various 
states and meanings