Bradford-White Corp B4 用户手册

下载
页码 32
Internet Version for Reference Only
 
BRADFORD WHITE
Page 30
Copper Brute B4 Volume Water Heaters
Page 31
Thermocouple
Thermocouple
Adapter
Gas Valve
Millivolt
Meter
Pilot
Figure 42.  Testing the pilot thermocouple.
5.2.16  Heater Will Not Shut Off
1.      If the heater stays on with the brown wire on the 
gas valve disconnected, replace the gas valve 
(see Section 4.2).
 
WARNING
Never attempt to repair the gas valve. Such 
attempts will void the warranty, and could lead to 
dangerous results. 
2.      Check electrical components for loose wires. 
Disconnect one of the lead wires on the gas 
valve. If the heater goes off, the wiring could be 
at fault. Repair or replace as necessary.
5.2.17  On-Off Main Burner Cycling
The main burners cycling on and off can be 
caused by:
1.      Poor wind conditions on an outdoor installation.
2.      Pilot components out of position.
3.      Low gas pressure causing an improper pilot 
flame. 
The pilot flame may appear to be all right until 
the main burners come on, then the pilot flame shrinks. 
An undersized gas supply line may cause this. 
5.2.18  Testing the Terminal Strip/
External   Controls
The terminal strip has been included so the 
heater can be operated by various external controls not 
provided by Bradford White. Determine whether or 
not an external control is open by checking for voltage 
at each terminal. If there is voltage at one terminal 
and not the other, examine the external control. It may 
require service or replacement. 
1.      Check all wire connections, ignition cable, and 
using a mirror, make sure there is a pilot flame. 
2.      If everything appears all right, measure flame 
sensing current by connecting a direct current 
(DC) microamp meter between terminal No. 
12 and the GND (BURNER) terminal on the 
ignition control (see Figure 43).
NOTE: Separate the microamp meter leads from 
each other and clear the heater chassis for most of their 
length to properly perform this test.
3.      When the pilot lights, the microamp meter should 
read 1.5 microamps or more with or without the 
main burners firing. A smaller current could be 
caused by poor pilot flame, the position of the 
pilot electrode, or bad cable and connectors.
4.      If the pilot flame and sensor electrode are all 
right, but there is no main burner ignition, clip 
one lead from a volt meter between the yellow 
wire terminal on the transformer and the brown 
wire terminal on the gas valve. 
5.      If the voltmeter reads between 20 to 28VAC, 
but the main burners do not fire, replace the gas 
valve (see Section 4.2).
5.2.15  Testing for Burner Ignition 
  (for standing pilot)
If the pilot flame and pilot thermocouple 
generator are all right, but there is no main burner 
ignition:
1.      Clip one lead of a volt meter between the yellow 
wire on the transformer and the brown wire 
terminal on the gas valve. 
2.      If the volt meter reads between 20 to 28VAC, 
but the main burners do not fire, replace the gas 
valve (see Section 4.2).
Figure 43.  Flame sensing current.