7 - GAS SUPPLY PIPING
7.1 General
• Use piping materials and joining methods acceptable 
to authority having jurisdiction.  In absence of such 
requirements:
• USA - National Fuel Gas Code, ANSI Z223.1/NFPA 
54
• Canada - Natural Gas and Propane Installation Code, 
CAN/CSA B149.1
• Size and install gas piping system to provide suffi cient 
gas supply to meet maximum input at not less than 
minimum supply pressure. See Table 6.
• Support piping with hooks straps, bands, brackets, 
hangers, or building structure components to prevent or 
dampen excessive vibrations and prevent strain on gas 
connection.  Boiler will not support piping weight.
• Use thread (joint) compound (pipe dope) suitable for 
liquefi ed petroleum gas.
• Provide sediment trap up stream of gas valve.
• Install manual main shutoff valve outside of jacket. See 
fi gure 16.
7.2  
Conversion To LP
Refer to Gas Conversion Kit Instructions.
CAUTION
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use 
any phone in your building.
• Immediately call your gas supplier from a 
neighbor’s phone.  Follow gas supplier’s 
instructions. 
• If you cannot reach your gas supplier, call the fi re 
department.
!
!
  
Figure 16  Manual Main Gas Shutoff Valve 
Outside Boiler Jacket
With Manufacturer Suggested Piping With Drip Leg
Manufacturer suggested gas piping with drip leg. 
Gas Supply Pressure
Natural Gas
Min.
Max.
3.5" w.c. 
(0.7 kPa)
14" w.c. (3.3 
kPa)
Table 6 - Gas Supply Pressure 
DANGER
Fire Hazard.  Do not use matches, candles, open 
fl ames, or other methods providing ignition source. 
Failure to comply will result in death or serious 
injury.
!  
7.3
 Leak Check Gas Piping
Pressure test boiler and gas connection before placing 
boiler in operation.
• Pressure test over 1/2 psig (3.5 kPa).  Disconnect 
boiler and its individual gas shutoff valve from gas 
supply system.
• Pressure test at 1/2 psig (3.5 kPa) or less.  Isolate 
boiler from gas supply system by closing manual gas 
shutoff valve. See fi gure 16.
• Locate leakage using gas detector, noncorrosive 
detection fl uid, or other leak detection method 
acceptable to authority having jurisdiction.  Do not use 
matches, candles, open fl ames, or other methods that 
can provide ignition source.
• Correct leaks immediately and retest.
Nipple           
¾” x 3” NPT
Tee ¾” NPT 
Nipple ¾ x 
3” NPT
¾” Pipe Cap
Gas 
Connection
¾” Gas 
Shutoff 
Valve in ON 
Postion
Nipple  
¾ x 3” 
NPT