8 - ELECTRICAL CONNECTIONS
8.1 General
Electrically bond boiler to ground in accordance with       
requirements of authority having jurisdiction.  Refer to:
• USA- National Electrical Code, ANSI/NFPA 70.
• Canada - Canadian Electrical Code, Part I, CSA C22.1: 
Safety Standard for Electrical Installations.
8.2 Line Voltage Connections - Boiler
Provide individual 120V, 15 amp circuit (recommended) 
with fused disconnect or service switch as required by 
authority having jurisdiction.
WARNING
Electrical shock hazard.  Turn OFF electrical power 
supply at service panel before making electrical  
connections.  Failure to do so could result in death 
or serious injury.
!
     
8.3 Central Heating Thermostat
A.  Use thermostat or boiler system control with 
dry contacts rated 0.5 amps @ 120 VAC.
 
Boiler 
control does not provide 24 VAC power to central 
heating thermostat. Do not use to power 24VAC 
thermostat.
B.  Locate and install thermostat per manufacturer's 
instructions. Maximum wire length is
 
330 ft (100m) 
for 22 ga. wire.
C.  Connect wires to terminals 1 and 2 as shown in 
fi gure 17. Wires are interchangeable.
Figure 17  - Terminal Block
2
 1
  - Thermostat or dry contacts
 2
  - 138 = Optional External Outdoor Reset Sensor
                  Connections on 5 & 6 terminals
        155 = Optional Indirect Tank Sensor  
                  Connections on 7 & 8 terminals
        370 = Low Water Cutoff (LWCO) - fi eld source              
                  Connections on 1 & 2 terminals are 120 Volts A/C.
                  Connections on 3 & 4 are dry contact only.