Tiered Configurations 
 
136
 
 
 
Tiered Configurations 
Standard Tiered Configurations 
Common Guidelines for Tiering Configuration 
•  Only Paragon I with hardware version HW3 (running Paragon II 
code) or Paragon II Main Unit can serve as Base Units (first tier). 
•  The version of Base Unit(s), both hardware and firmware, must 
always be later than or at least equal to the version of other tiered 
devices. 
•  A maximum of three tiers, including the Base Unit, is permitted. 
•  Devices that are not Paragon switches but come with two or more 
channel ports, such as Raritan MasterConsole, CompuSwitch, Z‐CIM, 
or P2ZCIM, are treated as tiered devices. These devices cannot act as 
Base Units in a Paragon II system and can be connected only to a Base 
Unit or to a second‐tier Paragon switch. 
Note: The easiest way to determine if the hardware version of your 
Paragon I unit is HW3 is to check the number of its stacking ports on the 
rear side. If there is only one stacking port, the hardware version is HW3. 
Guidelines for Single Base Configuration 
A single base configuration could be two‐tier or three‐tier configuration. 
It is composed of one Paragon Main Unit, serving as the Base Unit, and 
second‐tier or even third‐tier device(s). 
Initialization 
•  After all devices have been connected, power on the devices from 
UPPER tier to lower tier. For example, power on the second‐tier 
device(s) first and then the Base Unit in a two‐tier configuration. 
•  After initialization, each tiered device has an updated database. 
Guidelines for changing connections of tiered devices: 
Example A: Relocating a higher‐tier device (refer to dotted line) 
1.  Disconnect some or all of the user ports on the third‐tier unit 
(UMT‐3A) that connect to the channel ports of the second‐tier unit 
(UMT‐2A) and re‐connect the user ports to the channel ports of 
another second‐tier unit (UMT‐2B). 
2.  Recycle the power of all impacted devices. This is recommended to 
build a clean database for Paragon switches. Sequence of recycling 
power is from the HIGHEST tier (third tier) to the Base Unit. In our 
example: UMT‐3A Æ UMT‐2A Æ UMT‐2B Æ UMT‐1.