Utica Boilers SW Series II 安装指导
18
RATINGS AND DATA
TANKLESS WATER HEATER CAPACITIES
BOILER
MODEL
NUMBER
INPUT
RATE
G.P.H.
TANKLESS
HEATER
NUMBER
TANKLESS
HEATER CAPACITY
INTERMITTENT DRAW
G.P.M.
BOILER
WATER
CONTENT
GALS.
SW3065
.65
P3
CAPACITY AVAILABLE ON REQUEST
10.5
SW4100
1.00
T4
3.25
13.5
SW5125
1.25
T4
3.75
16.5
RATINGS AND DATA
BOILER
MODEL
NUMBER
OIL BURNER INPUT
(1)
HEATING
CAPACITY
AHRI NET
RATINGS
(2)
A.F.U.E.
G.P.H.
MBH
MBH*
WATER
MBH
RATING
SW3065
.65
91
78
68
85.0
SW4100
1.00
140
120
104
85.0
SW5125
1.25
175
150
130
85.0
NOTES:
1. AHRI burner input is based on an oil heating value of 140,000 Btu/gal.
2. Net AHRI Water Ratings shown are based on a piping and pickup allowance of 1.15. Consult
manufacturer before selecting boiler for installations having unusual piping and pickup requirements,
such as intermittent system operation, extensive piping.
3. 120 Volts, 15 Amps, & 60 Hz. required to operate this boiler.
STANDARD EQUIPMENT: Crated Boiler, Flush Jacket, Oil Burner, Target Wall/Liner, Circulator-1 1/4",
Safety Relief Valve, Temperature Pressure Gauge, Drain Valve, Wiring Harness, Burner Electrical
Disconnect, Plastic Cover, Supply Tapping 2", Return Tapping 1¼", High Limit and Circulator
Control, Primary Control. For Tankless Heater Units-add Tankless Hot Water Coil, Flow Restrictor
and Combination High Limit, Low Limit, and Circulator Control.