Utica Boilers SW Series II 安装指导

下载
页码 20
16
Check Safety Control Circuit after burner adjustments 
have been made for satisfactory performance.
INSTRUCTIONS TO OBTAIN PROPER OPERATION OF THE BOILER-BURNER UNIT
BECKETT SETTINGS
Boiler 
No.
Burner 
No.
Air 
Damp
Pin
Pump 
Pressure
Head
Nozzle 
Furnished
SW3065
AFII 100
3.25
3
140 PSI
HLX 6
.60 45B
SW4100
AFII 100
7.50
5
140 PSI
HLX 6
.85 45B
SW5125
AFII 150
5.00
8
140 PSI
HLX 6
1.10 45B
A.  HIGH LIMIT CONTROL: remove cover and note 
temperature setting. See fi gure 15 on page 15. With 
burner operating, decrease this setting to minimum 
point. When boiler water temperature exceeds this 
set point, high limit switch will open, shutting off 
power to oil burner and starting post purge cycle for 
approximately 2 minutes. Return setting to desired 
high limit point. Burner should restart. 
B.  PRIMARY CONTROL AND FLAME SENSOR:
To Check:
• Flame failure - simulate by shutting off oil supply 
with hand valve while burner is on. 15 seconds after 
fl ameout, safety switch locks out, ignition stops, 
motor stops and oil valve closes. To restart, open oil 
supply valve and reset safety switch.
• Ignition failure - with burner off, unplug electrical 
disconnect on burner harness. Disconnect one wire 
from transformer and put wire nut on disconnected 
wires .  Restore power and run through start-up 
procedure, safety switch should lockout as fl ame 
failure.  Reconnect wires after this procedure is 
complete.
• Power failure - Turn off main power supply switch 
while burner is operating. When burner stops, restore 
power and burner should start.
If operation is not as described as above, check wiring and 
controls.