Issue 07/04 
3  Functions 
MICROMASTER 420    Operating Instructions 
 
6SE6400-5AA00-0BP0 
69
 
3.5.3 
Calculating the motor / control data  
Internal motor / control data is calculated using parameter P0340 or, indirectly 
using parameter P3900 (refer to Section 3.5.2) or P1910 (refer to Section 3.5.4). 
The functionality of parameter P0340 can, for example, if the motor weight or the 
stator resistance is known. The following settings are possible for P0340: 
0 No 
calculation 
1 Complete 
parameterization 
For the complete parameterization (P0340 = 1), in addition to the motor / control 
parameters, parameters are also pre-assigned which refer to the motor rated data 
(e.g. torque limits and reference quantities for interface signals). 
Table 3-9 
Parameter for motor/control data 
P0344  Motor weight
P2002  Reference current
P2000  Reference frequency
P0350  Stator resistance (line-to-line)
P0611  Motor I2t time constant
P0346  Magnetization time
P1253  Vdc-controller output limitation
P0347  Demagnetization time
P1316  Boost end frequency
x
x
x
x
x
x
x
x
x
P0340 = 1
 
 
NOTE 
 
When exiting the quick commissioning with P3900 > 0 (refer to Section 3.5.2), 
internally P0340 is set to 1 (complete parameterization).  
 
For the motor data identification (refer to Section 3.5.4), after the measurement 
has been completed, internally P0340 is set to 3.