Issue 07/04 
3  Functions 
MICROMASTER 420    Operating Instructions 
 
6SE6400-5AA00-0BP0 
71
 
Motor data identification routine 
START
 
 
Factory setting: Bold 
 
 
 
 
 
 
Motortemp. - P0625
  @€  ± 5 °C ?
yes
no
Ambient Motor temp.
 5 °C
?
 
 
Allow the motor 
to cool down 
 
 
 
 
Ambient motor temperature 
(entered in °C) 
The motor ambient temperature is entered at the instant that motor data is 
being determined (factory setting: 20 °C).
 
The difference between the motor temperature and the motor ambient 
temperature must lie in the tolerance range of approx. ± 5 °C. If this is not 
the case, then the motor data identification routine can only be carried-out 
after the motor has cooled down.
 
P1910 = 1
 
 
Select motor data identification
 
  0 Disabled 
 
  1  Identification of all parameters with parameter change 
NOTE: 
For P1910 = 1  
  P0340 is internally set to P0340 = 1 and the 
appropriate data calculated (refer to parameter list P0340) 
 
 
ON 
 
 
Power-up the motor 
The 
ON command initiates the measuring operation. In so doing the motor aligns 
itself and conducts current. Alarm message A0541 (motor data identification 
routine active) is output.
 
A0541
 
 
After the motor data identification routine has been completed: 
 1.  P1910 is reset (P1910 = 0) 
 2.  A0541  is  withdrawn