Commissioning 
 
9.2 Procedure 
3. Select the motor 
Before the motor is selected, message 300701 "Commissioning required" must appear; see 
screenshot below. 
a) The torque motor appears in the list → Select the motor 
 
Figure 9-3 
Selection of a motor for which data has already been defined 
 
b) The torque motor does not appear in the list 
→ Select "NonSiemens mot.", enter the relevant data in the "Motor" field 
 
 
Note 
If a lower identification current is required (< 40%), bit 5 should be used to hide alarm 
300753 in MD 1012. 
 
 
1FW6 Built-in torque motors 
172
 
Configuration Manual, 05/2009, 6SN1197-0AD00-0BP7